Page 39 - GuardII+ Series 4208 Platform SM User Manual
P. 39

User Instructions




                      Parameter           Notes
                                          The unit being measured; i.e., “MW” or “kA”.
                      Unit                If “disabled” is selected as a unit, then that Operating Condition will not
                                             be read.
                                          The IP address of the Modbus data source.
                      IP Address
                                          This is supplied by the customer.
                                          The IP port number used to connect to the Modbus data source.
                                          The default value of 502 will be correct in most cases.
                      Port
                                          If a non-standard port number is needed, then the correct port number
                                             will be provided by the customer.
                                          The communication timeout used when establishing the connection to
                      Timeout                the Modbus data source.
                                          The default value of 500 ms will be correct in most cases.
                                          This determines the function code of the Modbus register.
                                          The default value of F03 Holding Register will be correct in most cases.
                      Function Code
                                          If a different function code is required, then the correct code will be
                                             provided by the customer.
                                          This determines the data type being read from the Register Address;
                      Data Format            i.e., ‘Signed 16-bit Integer” or “Float”.
                                          This is provided by the customer.
                                          This is used when multiple Modbus slave busses are connected to the
                                             same IP address.
                      Slave ID
                                          The default value of 1 will be correct in most cases.
                                          If a different Slave ID is required, it will be provided by the customer.
                      Register Address    This is the Modbus register address; it is provided by the customer.
                                          This is the translation formula used to convert the raw Modbus data to
                      Formula                the Unit selected.
                                          This is provided by the customer.

                        For the ambient humidity, there is also a checkbox to indicate if it is being acquired from
                     an ambient sensor connected to the monitor instead of a Modbus source.

                                     NOTE:
                                     If using a Remote I/O Unit, then the ASIM/DSIM configuration will be a
                                     more  collaborative  effort;  it  will  depend  on  the  exact  Remote  I/O  Unit
                                     assembly, which analog signals are connected to which inputs, and the
                                     translation from the analog signal to the actual Operating Condition being
                                     measured.