6.3. GuardII+ Configuration
Now that the GuardII+ has been attached to an asset, it can be configured.
NOTE:
The settings described represent typical settings used in an average
installation. Different installations may have custom requirements that are
not listed here; the SM sensors will vary from installation to installation.
• To start configuration, select the GuardII+ monitor and then press ‘Configure’. IAM will
connect to the monitor and show the configuration.
Figure 6-15 Configure GuardII+
6.3.1. General Configuration
Every GuardII+ has four common pieces of configuration information. These are
accessible on the ‘General’ configuration part of the application:
• Ethernet Address – enter the static IP address that the monitor will use. If an Ethernet
gateway is not required, then a gateway address of “255.255.255.255” will disable it.
• Alert Relay contact behavior – this is set for either “Disabled”, “Normally Open
Latching”, “Normally Open Momentary”, “Normally Closed Latching” or “Normally
Closed Momentary”.
• Line Frequency – this is the operating frequency of the asset being monitored.
• Clock synchronization – this is used to set the clock in the monitor when the settings
are uploaded. The clock can either be set to match the computer used for the
configuration or set to a specific time-zone.