Page 54 - GuardII+ Series 4208 Platform SM User Manual
P. 54

Troubleshooting



              7.2.3.  SM Terminations

                        If there is a sudden change in the SM data, use a digital voltmeter to measure the voltage
                     on the inputs of the SM card:

                                     NOTE:
                                     A sudden drop in ground brush readings or a low voltage measured from
                                     the ground input of the Termination does not necessarily indicate a failure
                                     of the GuardII+ or the Termination; this could indicate a genuine brush
                                     failure.

                        •  The Termination Power output should read 24 Vdc.

                        •  The Current and Voltage inputs should read an RMS voltage between 0-2.5 Vac.
                        •  If the readings are not correct, contact Iris Power LP Technical Support for assistance.
                        If one of the voltage signals is reporting a ‘clipped’ result, then the signal coming from the
                     Termination Box is too large.
                        •  Change the voltage selection fuse to an appropriate sensitivity, then change the sensor
                            sensitivity in IAM and upload the changes.

              7.2.4.  Alternate Monitor

                        If a second GuardII+ is available, this can be used for validating that the sensors are
                     working properly.  Run a measurement using the alternate device and compare the results to
                     the GuardII+.
                        •  If the results are similar, then both devices are likely working properly.

                        •  If the results are significantly different, then there is likely a problem with one of the
                            devices.

              7.3.  Iris Power LP Contact Information


                             Email:      Technical Support – techsupport.iris@qualitrolcorp.com
                                         General Inquiries – info@irispower.com
                                         Sales – sales.iris@qualitrolcorp.com
                                         Field Service – fs.admin@irispower.com
                                         Field Service Scheduling – scheduling@irispower.com
                             Phone:      +1-905-677-4824
                                         Between 09:00 and 17:00 (GMT-5hrs)
                             Fax:        +1-905-677-8498
                             Address:    Iris Power LP
                                         3110 American Drive
                                         Mississauga, ON L4V1T2
                                         Canada

                        If  technical  support  is  required,  please  provide  the  following  information  (the  more
                     information about the issue, the faster the resolution):





                                                              48
                                                                                          www.irispower.com
   49   50   51   52   53   54   55   56   57   58   59