Page 52 - GuardII+ Series 4208 Platform SM User Manual
P. 52

Troubleshooting



                     properly.  For rapid resolution of any Technical Support issue, this should be included on any
                     Technical Support inquiry.
                        Any basic diagnostic failure will cause the Error indicator on the front panel to be blink
                     orange; so, if the Error indicator is blinking orange, the basic diagnostics should be the first
                     thing to check.















                                            Figure 7-1 Front Panel Error Indicator

              7.1.2.  Advanced Diagnostics
                        More detailed diagnostics are available on a USB drive after downloading data from the
                     monitor  as  described  in  Section  6.4.2.    These  diagnostics  include  detailed  event-based
                     information over the lifetime of the device such as reboots and measurement status.

                        If it is convenient, this could be included on any Technical Support inquiry, but typically
                     would not be necessary for resolving most issues.

              7.2.  SM Measurement

                        If there are no measurements downloaded from the Archive, this may indicate a problem
                     with the SM card.  With the daily Archiving scheme described in Section 4.4, there should be
                     at least two sets of data stored every day.

                        The most obvious sign of a problem are the measurements that are being saved:
                        •  If measurement results show a sudden change, this could indicate a problem with the
                            monitor or the sensors and termination box.
                                     NOTE:
                                     A change in data does not automatically mean a problem with the SM
                                     system it could be caused by multiple issues including but not limited to:

                                       •  If the asset is not running, there will be a drop in signal level.
                                       •  Maintenance activities on the asset can cause a significant change
                                          in signal levels.
                                       •  A legitimate shaft grounding brush failure also causes a change in
                                          signal levels.

                        •  If measurement results show a ‘clipped’ quality flag in SMView, this likely indicates that
                            it is time to change the sensitivity.





                                                              46
                                                                                          www.irispower.com
   47   48   49   50   51   52   53   54   55   56   57