Page 33 - Basic PD Theory
P. 33

PD Data Types


               In phase-resolved analysis, the reference voltage usually         Bipolar Slot Total
               chosen for a given measurement is the phase-to-ground   0 to 3.16 pps  3.16 to 10 pps  10 to 31.6 pps  31.6 to 100 pps
               voltage of the phase subjected to on-line testing.  Please note   100 to 316 pps  316 to 1000 pps  > 1000 pps  Subset 8
               that the major unit division of the pulse phase scale (the x-  30                          30
               axis) is 45° and the minor unit division is 15°.  This allows for   20                     20
               quick identification of the phase angle value at which a given   10                        10
               PD cluster is  centred.   Specifically, this allows for quick   0                          0
                                                                 Pulse Magnitude [mV]
               discrimination between slot and inter-phase partial discharge
               sources [see Section 7.1 on Slot-based (Classic PD)]     -10                               -10
                                                                 -20                                      -20
               The standard LPD report  contains six graphs  organized in
               three rows, one for each phase, and two columns, one per PD   -30                          -30
               classification.  The data can be displayed in Standard form,   0  45  90  135  180  225  270  315  360
                                                                                Phase Angle [deg]
               where all three phases are shown relative to their respective   Figure 34: LPD or PRPD plot
               phase-to-ground voltages (Figure 35); or in phase-shifted form,
               where the first row of graphs displays data measured on one phase with no phase shift, and the second row of graphs displays
               data measured on the second phase but with the phase-angle scale shifted 120° from the first phase. The third row of graphs
               displays data measured on the third phase shifted 240° from the first phase (Figure 36).  Thus, the sinusoidal phase voltages are
               displayed as they occur simultaneously in time.  This allows for quick identification of phase-to-phase  voltage  dependent
               discharge sources and cross-coupled PD clusters.  In this configuration pulses from the same source, such as inter-phase arcing
               or cross-coupling will align vertically.










































                                                                                 www.irispower.com


                                                                                  30 | P ag e
   28   29   30   31   32   33   34   35   36   37   38