Page 30 - Basic PD Theory
P. 30

PD Data Types




                                            PD                   PT Cubicle  External noise  Breaker
                                                     Delay
                                Generator
                                                80pF                  80pF



                                                        Same
                                               L1      Length    L1


                                                       M  S
                                                    TGA - B

                                     Figure 28: Directional Time-of-Arrival Disturbance Separation
               3.4.2.2.3   Directional – (SSC)
                Like the Directional (BUS) installation, the SSC installation has two sensors, one on each end of the antenna.  It categorizes
               pulses by the direction of arrival.  The delay time between pulse arrivals is part of the sensor design and does not require
               calibration during installation.    Pulses arriving at the “Endwinding” sensor first are classified as  “Endwinding PD”, pulses
               arriving at the “Slot” sensor first are classified as “Slot PD”, while those arriving at both sensors within the Delay time are called
               “Under PD”.  (See Appendix E.  Zone of Coverage)

               3.4.2.3  Pulse Shape
               3.4.2.3.1   SSCs
               Experiments show that internal disturbances, such as
               core iron arcing, when detected by an SSC, have a
               pulse width > 8ns, whereas PD in the slot has a pulse
               width <6ns.  The TGA-S instrument, in addition to
               the directional separation described above, measures
               the width of each pulse and classifies it as either PD,
               wide pulses or noise pulses (width > 20ns or
               oscillatory).
                                                                          Figure 29:  Single-ended Installation
               3.4.2.4  Single-ended
               In some installations, particularly motors and smaller generators, the unit is connected to the power system with a relatively long
               power cable.  If the power cable is longer than about 30 metres (about 100 feet), the high frequency disturbances from the power
               system may be severely dispersed and attenuated when detected at the machine terminals.  Thus, if a pulse observed at the
               machine terminals has a fast rise time it is probably PD; whereas if it has a long rise time, it is likely a disturbance.  In these cases,
               only one coupler per phase, or three per unit, is necessary.  This is often referred to as a “single-ended installation” as shown in
               Figure 29.  There is no calibration required, though a sensitivity check is recommended.
               This configuration is used for  PDTrac  or  PDTracII monitors, but can also be  used with a  TGA-B or PDA-IV  portable
               instrument.










                                                                                 www.irispower.com


                                                                                  27 | P ag e
   25   26   27   28   29   30   31   32   33   34   35