Page 52 - Basic PD Theory
P. 52

PD Investigations


               7.2.1   Phase-to-phase  PD
               Phase to Phase discharges are described in Sections 1.4 and 2.4.7.4. Electrical field distribution controls partial discharge.
               Several PD sources may be found that are dependent upon  phase-to-phase electrical stress.  Often the presence of these
               discharge sources can be related to Contamination, Phase to phase discharges, poor contact between the semicon and the field-
               graded area or,  as in the case  of PD in the groundwall insulation, poorly impregnated windings.  Although most of the
               mentioned phenomena give rise to surface discharges, as opposed to discharges internal to the insulation, these phenomena may

                                C





                                               30º phase-         Yes       Phase-to-
                                                shifted?                    phase PD






               eventually lead to a phase-to-phase or phase-to-ground failure.  It should be mentioned that discharge activity on the ring bus or
               between phase leads is also phase-to-phase dependent discharge activity.
               Since the fields in the endwinding area are phase-to-phase voltage
               dependent and the electrical fields in the slot area are phase-to-ground
               voltage, it is often possible to distinguish between discharge activities
               occurring in the slot part versus the endwinding part of the winding
               using Phase Resolved Plots [see Section 4.3].  By creating an LPD for
               each phase of a given machine, with the reference phase-to-ground
               voltage shifted 120°  between  phases  based on phase rotation, the
               discharge activity will be presented in the time domain (Figure  36).
               Phase-to-phase voltage dependent PD pulses will be ± 30° phase shifted
               from the positions of phase-to-ground PD, and centred at 15°, 75°, 195°
               and 255° positions along the reference sine wave, based on the phase
               rotation of the machine. Phase-to-phase activity is only confirmed by
               these pulse positions if  the corresponding  pulse patterns in the two
               phases at the same time are approximately equal in magnitudes and also
               have opposite polarities, as shown in Figure 47. For example, PD in one
               phase will be centred on 75° while the PD in the other phase must be
               centred on 195° of the AC cycle.
               Although these pulses tend to be more erratic, it is sometimes possible
               to distinguish these pulses from others by observing their location with
               reference to the phase-to-ground voltage.  Since this activity is frequently
               isolated to a specific area of the machine, the PD pattern may reveal
               which phases are involved.  This is only possible if the two affected   Note the opposite polarity of  the clusters in the two
               phases both have detectable endwinding activity and their respective 30°   phases.
               phase shifts correspond to  what would be expected according to the
               machine rotation  (Figure  47).   Sometimes  this PD may be occurring   Figure 47: Phase-to-phase Discharges
               between a top and bottom coil in a slot, and visual verification of the
               activity may be difficult.



                                                                                 www.irispower.com


                                                                                  49 | P ag e
   47   48   49   50   51   52   53   54   55   56   57