Page 56 - Basic PD Theory
P. 56

PD Investigations


               7.3.3.1  Excitation pulses
               PD couplers sometimes detect the high frequency thyristor-firings of static excitation systems.  These pulses are usually of equal
               pulse repetitions, low magnitudes and occur repetitively across the AC cycle (Figure 51).  Usually, they are only discernible when
               there is low PD activity on the unit and the test range of the PD   Bipolar Machine PD
               test instrument is set to its most sensitive (lowest range) setting.    0 to 3.16 pps  3.16 to 10 pps  10 to 31.6 pps  31.6 to 100 pps
               This is not usually indicative of a problem with a stator winding,   100 to 316 pps  316 to 1000 pps  > 1000 pps  Subset 8
               but if pulse levels are high this may indicate that there is a   75                         75
               problem in the exciter.  Although this type of pattern is called   50 V]                    50
               “excitation pulses”, similar signals may also be  detected from   25                        25
               machines close to variable frequency  drives in the electrical
               system.                                             Pulse M agnitude [m  0                  0
                                                                   -25                                     -25
                    Disturbance pulses are not indicative of PD    -50                                     -50
                       sources within the winding insulation.      -75                                     -75
                                                                      0   45  90  135  180  225  270  315  360
                                                                                 Phase Angle [deg]
               7.3.3.2  Cross-coupling                                     Figure 51: Excitation Pulses
               PD pulses are high frequency pulses that may capacitively couple
               from one phase to another across the endwinding or circuit rings.  In addition, a coupler connected to one phase may detect
               pulses radiated from a source on another phase.  This behaviour is called cross-coupling and can be detected by observing PD
               pulses shifted  ± 120° from the positions of the source PD.  Phase-to-ground PD cross-coupled from another phase would
               cluster at 345°, 105°, 165° or 285°.  Cross-coupled inter-phase activity would be ± 30° phase-shifted from these positions as
               shown for C-phase (middle plot at 315°) in Figure 36.
               Cross-coupled PD is dependent on the geometry of the stator winding and does not necessarily indicate a problem with the
               insulation.  Additionally, based on the mode of pulse travel, the pulses may invert in polarity.

                                        Cross-coupled pulses are not indicative of PD sources,
                                   and therefore, are not usually associated with ageing mechanisms.


               7.3.3.3  Broadband Clusters
               Due to the physical attributes of some installations, there may
               be sources of low-magnitude broadband clusters detected by
               the couplers.  When this situation exists, the pulses are low in
               magnitude and normally manifest themselves across the AC
               cycle  (Figure  52).   In some instances, the magnitude of the
               detected pattern could be reduced when a more reliable (or
               shorter) ground path for the PD couplers was chosen.
               Typically the magnitude of this activity is quite low and as the
               winding ages, PD originating within the winding will reach
               higher magnitudes and be visible beyond this  noise-like
               disturbance.                                               Figure 52: Broadband Clusters

                                         Broadband clusters are not indicative of PD sources
                                     within the winding or problems with the PD detection system.








                                                                                 www.irispower.com


                                                                                  53 | P ag e
   51   52   53   54   55   56   57   58   59   60   61