Page 60 - Basic PD Theory
P. 60

Off-line Testing




 A.    Off-line Testing



 Test   Description   Detects   Effectiveness   Typical Test   Test Precautions   References
                          Frequency (Years)
 AC High Potential  Overvoltage Test   Weakened ground   Pass/Fail:  Not effective for   Factory test or as   Potentially destructive  IEEE 112 or NEMA
 applied from conductor- insulation, severe cracks   trending   necessary following   MG-1, IEEE 432
 to-ground                major maintenance
 Capacitance   AC test to measure   Moisture and tape   Single coils during   Factory test      IEEE 286
 insulation capacitance   delamination or improper  manufacturing of medium
 line-to-ground   curing   voltage generators.
 Coil-to-ground   Measure resistance from  Detects problems with the  Pass: <2000Ω   QA test
 resistance   the coil to the core   semicon or interference fit   Fail: >5000Ω
 DC High Potential  Overvoltage Test   Weakened ground   Step Voltage or Ramp   As necessary   Potentially destructive  IEEE 95 or NEMA
 applied from conductor- insulation, severe cracks   Method effective for trending   MG-1
 to-ground
 Dissipation Factor  AC test to measure   Moisture and tape   Single coils during   1-2      IEEE 286
 & Tip-up - Medium  dissipation line-to-  delamination or improper  manufacturing of medium
 Voltage generators  ground   curing   voltage generators.  Possible
 for trending.
 Endwinding   Measure frequency   Loose or resonance of   Look for high resonance at   As needed
 response   response    endwinding   100/120Hz
 Insulation   Insulation between   Contamination, or   Trending if corrected for   1-1.5 after outage       IEEE 43
 Resistance   conductor and ground  moisture   temperature
 Partial discharge   AC test to measure   Moisture and tape   With some technologies   1-1.5       IEEE 1434
 partial discharge line-to- delamination or improper  possibly effective for
 ground    curing   trending
 Polarization Index  Ratio of 10-minute IR to Wet or dirty insulation,   Effective for trending   1-1.5       IEEE 43
 1-minute IR   possibly aged insulation
 Power Factor &   AC test to measure   Moisture and tape   Single coils during   1-2       IEEE 286
 Tip-up - Medium   power factor line-to-  delamination or improper  manufacturing of medium
 Voltage generators  ground    curing   voltage generators.  Possible
 for trending.









    56 | P ag e