Page 58 - Basic PD Theory
P. 58

PD Investigations


               7.4  Summary - Failure Processes
                     Failure mechanism      Polarity      Load Effect   Temperature Effect   Phase Location
                    Internal delamination   No predominance   None          Inverse          45° and 225°

                      Thermal cycling       Negative         None           Inverse             45°

                                          No or negative
                    Manufacturing defect                     None           Inverse          45° and 225°
                                          predominance
                    Bar/coil movements      Positive        Direct          Inverse             225°
                   Electrical slot discharge   Positive      None           Direct              225°

                     Contamination or    No predominance     None         Unpredictable   15°, 75°, 195°, 255°,
                     Electrical tracking                                                     can be erratic
                                                                                                225°,
                     Interface problem    Mostly positive    None           Direct
                                                                                            can be 0°/180°
                     Gap-type discharge                                                        0° - 90°,
                        (Open air)       No predominance   Unknown         Unknown            180° - 270°

                    Vibration sparking *   No predominance   Direct         Inverse            Erratic

                                                                                          Sometimes 0°/180°,
                      Broken strands *   No predominance    Direct         Unknown
                                                                                             can be erratic
                         * Will only be seen in PD measurements if it is occurring at or near the phase line ends or it is
                          near the neutral connection and an EMC is installed there.
                   Endwinding Vibration   No PD associated with this process

                   Internal Water Leak   No PD associated with this process




























                                                                                 www.irispower.com


                                                                                  55 | P ag e