240 DURABILITY
      • Concrete: Proprietary to BS 8500
          - Conformity: To BS 8600-2.
          - Identity: Contractor's choice.
          - Additional requirements: site specific.
          - Exposure class to BS 8500: site specific.
             Submit: Proof that the concrete conforms to the recommendations of BS 8500-1
             A5.

261 COVER WHEN USING NATURAL STONE FACING
      • Natural stone facing qualifying thickness (minimum): 25 mm.
      • Nominal minimum concrete cover to exposed face of panel: 20mm.

270 DIMENSIONAL COORDINATION
      • Detailing cladding: Comply with the requirements for accuracy in manufacture
          and erection, and accommodate deviations in support structure.
      • Fixings/ fasteners: Select to give sufficient three dimensional adjustment.
      • Proposals to achieve required tolerances: Submit.

           MAKING CONCRETE

310 CONCRETE MIXES GENERALLY
      • Production of concrete: To BS 8500 and BS EN 206-1.
      • Chloride ion content of mix constituents: Not to exceed 0.4% of weight of cement.
      • Admixtures containing calcium chloride: Not allowed.
      • Sampling rate for compressive strength testing: Not less than one sample for each
          day of use.

330 MIXES FOR VISIBLE FACES
      • Constituent materials and mix design: To remain constant for each finish type.
      • Panel colour and appearance: To be consistent for each finish type.
      • Aggregates: To be of consistent colour, free of deleterious materials that cause
          popping and staining.
          - Origin: Single source for each finish type having sufficient quantity for whole
             contract.

          MANUFACTURE

420 MANUFACTURING ACCURACY
      • Standard: To BS 8297, table 11 and to allow compliance with clause 630.

430 FIXINGS
      • Materials generally: Nonferrous metal.
          - Stainless steel: Austenitic in accordance with BS 8297, clause 4.3.3.1.
          - Allowable alternative: Galvanized steel when located away from external faces
             or edges.
      • Lifting devices: Mild steel permitted when mortar cover will provide the same
          protection required for reinforcement in the panel.
      • Bimetallic corrosion and staining: Prevent by appropriate selection and use of
          materials.

RotF generic (intermediate) NBS 2014  6118-AEW-XX-XX-NBS-A-01