Reference Guide                                                         Fire Strategy



               floor, in accordance with information provided by Co-op and taking account of the

               recommendations of ADB Table C1. This value is further in accordance with Table 9 of
               BS9999:2017.

                                     Usage                             Floor Space Factor (m2/person)

                                  Shop sales area                               4.0
                                     Office                                     6.0
                              Storage and Warehousing                           30.0

               Where a given population is known, for example number of staff likely to be present at any
               one time, this value may be taken in lieu of an occupancy calculation undertaken. For

               example, a store with 400m2 of free shop sales area may be allocated a population of 100
               persons (400/4.0) plus a notional allowance of 5 members of staff.

                   1.4.3 Fire Exits


               Where the anticipated population of a building, or part thereof, is >60 persons, ADB requires
               that an alternative escape route is provided. Where two distinct exits are provided, it is

               reasonable to assume that one of these may become unusable in the event of a fire, and it
               follows that each individual exit should have sufficient capacity to accommodate the
               population of the entire floorplate.


               The following table outlines the exit capacity of exits from a given width:

                                  Maximum number of persons      Minimum width (mm)

                                              60                         750
                                             110                         850
                                             220                        1,050
                                         More than 220              5mm per person

               Note: the above requirements do not take account any further limitations stipulated in
               Approved Document M: Access to and Use of Buildings.