          Reverse Power Continued





              regulator output is at 63 volts (Max voltage) it cannot ex-
              cite the generator anymore and goes into reverse power.
              To determine if the generator has 1 or multiple bad diodes
              is to measure the F+ (red probe) to F- (black probe) volts
              DC on the back of the regulator  (NOTE:  Ensure  the
              probes  do  not  come  in  contact  with  each  other.)
              with the engine running unloaded or online (small load). If
              the diodes are bad, it will need more field excitation, 20 or
              more  volts,  if  everything  is  good  it  will  be  more  like  10
              volts. The only difficulties is that the generator field wires
              need to remain connected to the back of the regulator. To
              take the measurements the wires need to be pulled off just
              enough to get the probes on the terminal (spade connect-
              ors).  The values listed are typical for a 1300KW generator- if
              abnormal  readings  are  measured  each  diode  will  need  to  be
              measured one at a time on the rectifier.