Page 116 - 2018_IRC
P. 116

FOUNDATIONS



               R403.1.1  Minimum  size.  The  minimum  width,  W,  and  R403.1.3.5.3 and extend not less than 14 inches (357
               thickness, T, for concrete footings shall be in accordance  mm) into the stem wall. Standard hooks shall comply
               with  Tables  R403.1(1)  through  R403.1(3)  and  Figure  with Section R608.5.4.5. Not fewer than one No. 4 hor-
               R403.1(1) or R403.1.3, as applicable. The footing width  izontal bar shall be installed within 12 inches (305 mm)
               shall be based on the load-bearing value of the soil in accor-  of the top of the stem wall and one No. 4 horizontal bar
               dance with Table R401.4.1. Footing projections, P, shall be  shall be located 3 to 4 inches (76 mm to 102 mm) from
               not less than 2 inches (51 mm) and shall not exceed the  the bottom of the footing.
               thickness of the footing. Footing thickness and projection
               for fireplaces shall be in accordance with Section R1001.2.  R403.1.3.2 Masonry stem walls with concrete foot-
               The size of footings supporting piers and columns shall be  ings.  In  Seismic  Design  Categories  D ,  D   and  D 2
                                                                                                            1
                                                                                                        0
               based on the tributary load and allowable soil pressure in  where a masonry stem wall is supported on a concrete
               accordance with Table R401.4.1. Footings for wood foun-  footing, not fewer than one No. 4 vertical bar shall be
               dations shall be in accordance with the details set forth in  installed at not more than 4 feet (1219 mm) on center.
               Section  R403.2,  and  Figures  R403.1(2)  and  R403.1(3).  The vertical bar shall have a standard hook and extend
               Footings  for  precast  foundations  shall  be  in  accordance  to the bottom of the footing and shall have support and
               with the details set forth in Section R403.4, Table R403.4,  cover as specified in Section R403.1.3.5.3 and extend
               and Figures R403.4(1) and R403.4(2).                    not less than 14 inches (357 mm) into the stem wall.
                                                                       Standard hooks shall comply with Section R608.5.4.5.
               R403.1.2 Continuous footing in Seismic Design Catego-   Not  fewer  than  one  No.  4  horizontal  bar  shall  be
               ries D , D  and D . Exterior walls of buildings located in  installed within 12 inches (305 mm) of the top of the
                     0
                        1
                              2
               Seismic Design Categories D , D  and D  shall be supported  wall and one No. 4 horizontal bar shall be located 3 to 4
                                         1
                                      0
                                               2
               by continuous solid or fully grouted masonry or concrete  inches (76 mm to 102 mm) from the bottom of the foot-
               footings.  Other  footing  materials  or  systems  shall  be  ing. Masonry stem walls shall be solid grouted.
               designed in accordance with accepted engineering practice.
               Required interior braced wall panels in buildings located in  R403.1.3.3 Slabs-on-ground with turned-down foot-
               Seismic Design Categories D , D  and D  with plan dimen-  ings.  In  Seismic  Design  Categories  D ,  D   and  D ,
                                                                                                                  2
                                                                                                           1
                                                                                                        0
                                       0
                                                2
                                          1
               sions greater than 50 feet (15 240 mm) shall be supported by  slabs-on-ground cast monolithically with turned-down
               continuous solid or fully grouted masonry or concrete foot-  footings shall have not fewer than one No. 4 bar at the
               ings in accordance with Section R403.1.3.4, except for two-  top and the bottom of the footing or one No. 5 bar or
               story buildings in Seismic Design Category D , in which all  two No. 4 bars in the middle third of the footing depth.
                                                   2
               braced wall panels, interior and exterior, shall be supported
               on continuous foundations.                                Where  the  slab  is  not  cast  monolithically  with  the
                                                                       footing, No. 3 or larger vertical dowels with standard
                  Exception: Two-story buildings shall be permitted to  hooks on each end shall be installed at not more than 4
                  have interior braced wall panels supported on continu-  feet  (1219  mm)  on  center  in  accordance  with  Figure
                  ous foundations at intervals not exceeding 50 feet (15  R403.1.3, Detail 2. Standard hooks shall comply with
                  240 mm) provided that:                               Section R608.5.4.5.
                    1. The height of cripple walls does not exceed 4 feet
                       (1219 mm).                                      R403.1.3.4 Interior  bearing and  braced wall panel
                                                                       footings in Seismic Design Categories D , D  and D .
                                                                                                            1
                                                                                                         0
                                                                                                                  2
                    2. First-floor  braced  wall  panels  are  supported  on  In Seismic Design Categories D , D  and D , interior
                                                                                                     1
                                                                                                  0
                                                                                                            2
                       doubled floor joists, continuous blocking or floor  footings supporting bearing walls or braced wall pan-
                       beams.                                          els, and cast monolithically with a slab on grade, shall
                    3. The  distance  between  bracing  lines  does  not  extend to a depth of not less than 12 inches (305 mm)
                       exceed twice the building width measured paral-  below the top of the slab.
                       lel to the braced wall line.                    R403.1.3.5  Reinforcement.  Footing  and  stem  wall
               R403.1.3 Footing and stem wall reinforcing in Seismic   reinforcement shall comply with Sections R403.1.3.5.1
               Design  Categories  D ,  D ,  and  D .  Concrete  footings  through R403.1.3.5.4.
                                             2
                                  0
                                     1
               located  in  Seismic Design  Categories  D , D   and  D , as
                                                           2
                                                    1
                                                 0
               established in Table R301.2(1), shall have minimum rein-  R403.1.3.5.1 Steel reinforcement. Steel reinforce-
               forcement  in  accordance  with  this  section  and  Figure  ment shall comply with the requirements of ASTM
               R403.1.3.  Reinforcement  shall  be  installed  with  support  A615, A706 or A996. ASTM A996 bars produced
               and cover in accordance with Section R403.1.3.5.          from rail steel shall be Type R. The minimum yield
                                                                         strength  of  reinforcing  steel  shall  be  40,000  psi
                  R403.1.3.1 Concrete stem walls with concrete foot-     (Grade 40) (276 MPa).
                  ings. In Seismic Design Categories D , D  and D  where
                                                  1
                                                        2
                                                0
                  a construction joint is created between a concrete foot-  R403.1.3.5.2  Location  of  reinforcement  in  wall.
                  ing and a concrete stem wall, not fewer than one No. 4  The center of vertical reinforcement in stem  walls
                  vertical bar shall be installed at not more than 4 feet  shall be located at the centerline of the wall. Hori-
                  (1219 mm) on center. The vertical bar shall have a stan-  zontal and vertical reinforcement shall be located in
                  dard hook and extend to the bottom of the footing and  footings  and  stem  walls  to  provide  the  minimum
                  shall  have  support  and  cover  as  specified  in  Section  cover required by Section R403.1.3.5.3.
             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                                91
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.