CHIMNEYS AND FIREPLACES



         R1003.15  Flue  area  (masonry  fireplace).  Flue  sizing  for  R1003.15.2 Option 2. The minimum net cross-sectional
         chimneys serving fireplaces shall be in accordance with Sec-  area of the chimney flue shall be determined in accordance
         tion R1003.15.1 or R1003.15.2.                          with  Figure  R1003.15.2.  A  flue  size  providing  not  less
           R1003.15.1 Option 1. Round chimney flues shall have a  than the equivalent net cross-sectional area shall be used.
           minimum  net  cross-sectional  area  of  not  less  than  one-  Cross-sectional  areas  of  clay  flue  linings  are  shown  in
           twelfth  of  the  fireplace  opening.  Square  chimney  flues  Tables  R1003.14(1)  and  R1003.14(2)  or  as  provided  by
           shall have a minimum net cross-sectional area of one-tenth  the manufacturer or as measured in the field. The height of
           of the fireplace opening. Rectangular chimney flues with  the chimney shall be measured from the firebox floor to
           an aspect ratio less than 2 to 1 shall have a minimum net  the top of the chimney flue.
           cross-sectional area of one-tenth of the fireplace opening.  R1003.16 Inlet. Inlets to masonry chimneys shall enter from
           Rectangular chimney flues with an aspect ratio of 2 to 1 or  the side. Inlets shall have a thimble of fireclay, rigid refrac-
           more  shall  have  a  minimum  net  cross-sectional  area  of  tory material or metal that will prevent the connector from
           one-eighth of the fireplace opening. Cross-sectional areas  pulling out of the inlet or from extending beyond the wall of
           of clay flue linings are shown in Tables R1003.14(1) and  the liner.
           R1003.14(2)  or  as  provided  by  the  manufacturer  or  as
           measured in the field.




                                                                                                 3000

                                                                                                 2800

                                                                                                 2600

                                                                                                 2400

                        224    269                                                               2200
                                                                                                 2000

                        187    214                                                               1800
                       MIN. CROSS-SECTIONAL AREA (SQ. IN.)  140  168                             1400
                                                                                                 1600



                                                                                                 1200
                        110
                               124
                                                                                                 1000

                         76
                                                                                                 600
                         70
                                82
                         53     91                                                               800
                                58
                                                                                                 400
                         32     37
                                                                                                 200
                                                                    20
                                                                         21
                                                     17
                                                          18
                                                               19
                          ROUND  FLUES  SQUARE OR  RECTANGULAR  FLUES  13  14  15  16 HEIGHT, MEASURED FROM FLOOR  22  23  24  25 FIREPLACE  OPENING AREA  (SQ. IN.)
                                                   OF COMBUSTION CHAMBER TO
                                                        TOP OF FLUE (FT)
                                             2
          For SI: 1 foot = 304.8 mm, 1 square inch = 645.16 mm .
                                                     FIGURE R1003.15.2
                                             FLUE SIZES FOR MASONRY CHIMNEYS