CHIMNEYS AND FIREPLACES



             R1003.17 Masonry chimney cleanout openings. Cleanout  R1003.19 Chimney fireblocking. Spaces between chimneys
             openings shall be provided within 6 inches (152 mm) of the  and floors and ceilings through which chimneys pass shall be
             base of each flue within every masonry chimney. The upper  fireblocked with noncombustible material securely fastened
             edge of the cleanout shall be located not less than 6 inches (152  in place. The fireblocking of spaces between chimneys and
             mm) below the lowest chimney inlet opening. The height of  wood joists, beams or headers shall be self-supporting or be
             the opening shall be not less than 6 inches (152 mm). The clea-  placed on strips of metal or metal lath laid across the spaces
             nout shall be provided with a noncombustible cover.  between combustible material and the chimney.
               Exception:  Chimney  flues  serving  masonry  fireplaces  R1003.20  Chimney  crickets.  Chimneys  shall  be  provided
               where cleaning is possible through the fireplace opening.  with crickets where the dimension parallel to the ridgeline is
             R1003.18 Chimney clearances. Any portion of a masonry chim-  greater than 30 inches (762 mm) and does not intersect the
             ney located in the interior of the building or within the exterior  ridgeline.  The  intersection  of  the  cricket  and  the  chimney
             wall of the building shall have a minimum airspace clearance to  shall  be  flashed  and  counterflashed  in  the  same  manner  as
             combustibles of 2 inches (51 mm). Chimneys located entirely out-  normal  roof-chimney  intersections.  Crickets  shall  be  con-
             side the exterior walls of the building, including chimneys that pass  structed  in  compliance  with  Figure  R1003.20  and  Table
             through the soffit or cornice, shall have a minimum airspace clear-  R1003.20.
             ance of 1 inch (25 mm). The airspace shall not be filled, except to    TABLE R1003.20
             provide  fire  blocking  in  accordance  with  Section  R1003.19.    CRICKET DIMENSIONS
                                                                          ROOF SLOPE                   H
               Exceptions:
                                                                             12:12                  1 /  of W
                  1. Masonry chimneys equipped with a chimney lining                                 2
                    system  listed  and  labeled  for  use  in  chimneys  in  8:12                  1 /  of W
                                                                                                     3
                    contact  with  combustibles  in  accordance  with  UL    6:12                   1 /  of W
                                                                                                     4
                    1777 and installed in accordance with the manufac-       4:12                   1 /  of W
                    turer’s instructions are permitted to have combusti-                            1  6
                    ble material in contact with their exterior surfaces.    3:12                    /  of W
                                                                                                     8
                  2. Where masonry chimneys are constructed as part of
                    masonry  or  concrete  walls,  combustible  materials          SECTION R1004
                    shall not be in contact with the masonry or concrete    FACTORY-BUILT FIREPLACES
                    wall less than 12 inches (305 mm) from the inside  R1004.1 General. Factory-built fireplaces shall be listed and
                    surface of the nearest flue lining.
                                                                  labeled and shall be installed in accordance with the condi-
                  3. Exposed combustible trim and the edges of sheath-  tions of the listing. Factory-built fireplaces shall be tested in
                    ing  materials,  such  as  wood  siding  and  flooring,  accordance with UL 127.
                    shall be permitted to abut the masonry chimney side
                    walls,  in  accordance  with  Figure  R1003.18,  pro-  R1004.2 Hearth extensions. Hearth extensions of approved
                                                                  factory-built fireplaces shall be installed in accordance with
                    vided such combustible trim or sheathing is not less  the listing of the fireplace. The hearth extension shall be read-
                    than 8 inches (203 mm) from the inside surface of  ily  distinguishable  from  the  surrounding  floor  area.  Listed
                    the nearest flue lining.
                                                                  and labeled hearth extensions shall comply with UL 1618.
























             For SI: 1 inch = 25.4 mm.
                                                         FIGURE R1003.18
                                                  CLEARANCE FROM COMBUSTIBLES