FUEL GAS


                       SECTION G2415 (404)                       member and not less than 4 inches (102 mm) below the top
                  PIPING SYSTEM INSTALLATION                     framing member.
         G2415.1  (404.1)  Installation  of  materials.  Materials  used  G2415.7.2 (404.7.2) Piping installed in other locations.
         shall be installed in strict accordance with the standards under  Where the piping is located within a framing member and
         which  the  materials  are  accepted  and  approved.  In  the  is less than 1 /  inches (38 mm) from the framing member
                                                                           1
                                                                            2
         absence  of  such  installation  procedures,  the manufacturer’s  face  to  which  wall,  ceiling  or  floor  membranes  will  be
         instructions shall be followed. Where the requirements of ref-  attached, the piping shall be protected by shield plates that
         erenced standards or manufacturer’s instructions do not con-  cover the width and length of the piping. Where the piping
         form to minimum provisions of this code, the provisions of  is located outside of a framing member and is located less
         this code shall apply.                                  than 1 /  inches (38 mm) from the nearest edge of the face
                                                                      1
                                                                       2
         G2415.2  (404.2)  CSST.  CSST  piping  systems  shall  be  of  the  framing  member  to  which  the  membrane  will  be
         installed in accordance with the terms of their approval, the  attached, the piping shall be protected by shield plates that
         conditions of listing, the manufacturer’s instructions and this  cover the width and length of the piping.
         code.                                                   2415.7.3 (404.7.3) Shield plates. Shield plates shall be of
         G2415.3  (404.3)  Prohibited  locations.  Piping shall  not  be  steel material having a thickness of not less than 0.0575
         installed in or through a ducted supply, return or exhaust, or a  inch (1.463 mm) (No. 16 gage).
         clothes chute, chimney or gas vent, dumbwaiter or elevator  G2415.8 (404.8) Piping in solid floors. Piping in solid floors
         shaft. Piping  installed  downstream  of  the  point of delivery  shall be laid in channels in the floor and covered in a manner
         shall not extend through any townhouse unit other than the  that will allow access to the piping with a minimum amount
         unit served by such piping.
                                                              of damage to the building. Where such piping is subject to
         G2415.4 (404.4) Piping in solid partitions and walls. Con-  exposure to excessive moisture or corrosive substances, the
         cealed piping shall not be located in solid partitions and solid  piping shall be protected in an approved manner. As an alter-
         walls, unless installed in a chase or casing.        native to installation in channels, the piping shall be installed
                                                              in a conduit of Schedule 40 steel, wrought iron, PVC or ABS
         G2415.5  (404.5)  Fittings  in  concealed  locations.  Fittings
         installed in concealed locations shall be limited to the follow-  pipe in accordance with Section G2415.8.1 or G2415.8.2.
         ing types:                                              G2415.8.1 (404.8.1) Conduit with one end terminating
           1. Threaded elbows, tees and couplings.               outdoors. The conduit shall extend into an occupiable por-
                                                                 tion of the building and, at the point where the conduit ter-
           2. Brazed fittings.                                   minates in the building, the space between the conduit and
           3. Welded fittings.                                   the gas piping shall be sealed to prevent the possible entrance
                                                                 of any gas leakage. The conduit shall extend not less than 2
           4. Fittings listed to ANSI LC1/CSA 6.26 or ANSI LC4/  inches (51 mm) beyond the point where the pipe emerges
              CSA 6.32.                                          from the floor. If the end sealing is capable of withstanding
         G2415.6  (404.6)  Underground  penetrations  prohibited.  the full pressure of the gas pipe, the conduit shall be designed
         Gas piping shall not penetrate building foundation walls at  for the same pressure as the pipe. Such conduit shall extend
         any  point  below  grade.  Gas piping  shall  enter  and  exit  a  not less than 4 inches (102 mm) outside the building, shall be
         building  at  a  point  above  grade  and  the  annular  space  vented above grade to the outdoors and shall be installed so
         between the pipe and the wall shall be sealed.          as to prevent the entrance of water and insects.
         G2415.7  (404.7)  Protection  against  physical  damage.  G2415.8.2 (404.8.2) Conduit with both ends terminating
         Where piping will be concealed within light-frame construc-  indoors.  Where  the  conduit  originates  and  terminates
         tion assemblies, the piping shall be protected against penetra-  within the same building, the conduit shall originate and
         tion  by  fasteners  in  accordance  with  Sections  G2415.7.1  terminate in an accessible portion of the building and shall
         through G2415.7.3.                                      not  be  sealed.  The  conduit  shall  extend  not  less  than  2
                                                                 inches (51 mm) beyond the point where the pipe emerges
           Exception: Black steel piping and galvanized steel piping
           shall not be required to be protected.                from the floor.
           G2415.7.1  (404.7.1)  Piping  through  bored  holes  or  G2415.9  (404.9)  Above-ground  piping  outdoors.  Piping
                                                                                                     1
           notches. Where piping is installed through holes or notches  installed outdoors shall be elevated not less than 3 /  inches (89
                                                                                                      2
                                                        1
           in framing members and the piping is located less than 1 / 2  mm) above ground and where installed across roof surfaces,
                                                                                        1
           inches (38 mm) from the framing member face to which  shall be elevated not less than 3 /  inches (89 mm) above the
                                                                                         2
           wall, ceiling or floor membranes will be attached, the pipe  roof  surface.  Piping  installed  above  ground,  outdoors,  and
           shall be protected by shield plates that cover the width of  installed across the surface of roofs shall be securely supported
           the pipe and the framing member and that extend not less  and located where it will be protected from physical damage.
           than 4 inches (102 mm) to each side of the framing member.  Where passing through an outside wall, the piping shall be pro-
           Where the framing member that the piping passes through  tected against corrosion by coating or wrapping with an inert
           is a bottom plate, bottom track, top plate or top track, the  material. Where piping is encased in a protective pipe sleeve,
           shield plates shall cover the framing member and extend  the annular space between the piping and the sleeve shall be
           not less than 4 inches (102 mm) above the bottom framing  sealed.