Page 605 - 2018_IRC
P. 605

FUEL GAS



                   adapter  risers  that  are  installed  in  accordance  5. The inside radius of a bend shall be not less than six
                   with the manufacturer’s instructions.           times the outside diameter of the pipe.
                2. Plastic pipe shall be permitted to terminate with a  G2416.3 (405.3) Plastic pipe. Plastic pipe bends shall com-
                   wall  head  adapter  within  buildings  where  the  ply with the following:
                   plastic  pipe  is  inserted  in  a  piping  material  for
                   fuel gas use in buildings.                    1. The pipe shall not be damaged and the internal diame-
                                                                   ter of the pipe shall not be effectively reduced.
                3. Plastic  pipe  shall  be  permitted  under  outdoor
                   patio, walkway and driveway slabs provided that  2. Joints shall not be located in pipe bends.
                   the burial depth complies with Section G2415.12.  3. The radius of the inner curve of such bends shall be not
           G2415.17.2  (404.17.2)  Connections.  Connections  made  less than 25 times the inside diameter of the pipe.
           outdoors  and  underground  between  metallic  and  plastic  4. Where the piping manufacturer specifies the use of spe-
           piping shall be made only with transition fittings conform-  cial bending tools or procedures, such tools or proce-
           ing to ASTM D2513 Category I or ASTM F1973.
                                                                   dures shall be used.
           G2415.17.3 (404.17.3) Tracer. A yellow-insulated copper
           tracer wire or other approved conductor, or a product spe-
           cifically designed for that purpose, shall be installed adja-    SECTION G2417 (406)
           cent to underground nonmetallic piping. Access shall be  INSPECTION, TESTING AND PURGING
           provided to the tracer wire or the tracer wire shall termi-
           nate above ground at each end of the nonmetallic piping.  G2417.1  (406.1)  General.  Prior  to  acceptance  and  initial
           The tracer wire size shall be not less than 18 AWG and the  operation, all piping installations shall be visually inspected
           insulation type shall be suitable for direct burial.  and  pressure tested  to determine that  the  materials,  design,
                                                              fabrication and installation practices comply with the require-
         G2415.18 (404.18) Pipe cleaning. The use of a flammable or  ments of this code.
         combustible gas to clean or remove debris from a piping sys-
         tem shall be prohibited.                                G2417.1.1 (406.1.1) Inspections. Inspection shall consist
                                                                 of visual examination, during or after manufacture, fabri-
         G2415.19 (404.19) Prohibited devices. A device shall not be  cation, assembly or pressure tests.
         placed inside the piping or fittings that will reduce the cross-
         sectional area or otherwise obstruct the free flow of gas.  G2417.1.2 (406.1.2) Repairs and additions. In the event
                                                                 repairs or additions are made after the pressure test, the
           Exceptions:                                           affected piping shall be tested.
              1. Approved gas filters.
                                                                   Minor repairs and additions are not required to be pres-
              2. An approved fitting or device where the gas piping  sure tested provided that the work is inspected and con-
                system has been sized to accommodate the pressure  nections  are  tested  with  a  noncorrosive  leak-detecting
                drop of the fitting or device.                   fluid or other approved leak-detecting methods.
         G2415.20 (404.20) Testing of piping. Before any system of  G2417.1.3 (406.1.3) New branches. Where new branches
         piping  is  put  in  service  or  concealed,  it  shall  be  tested  to  are installed to new appliances, only the newly installed
         ensure that it is gas tight. Testing, inspection and purging of  branches shall be required to be pressure tested. Connec-
         piping systems shall comply with Section G2417.         tions between the new piping and the existing piping shall
                                                                 be tested with a noncorrosive leak-detecting fluid or other
                                                                 approved leak-detecting methods.
                       SECTION G2416 (405)
            PIPING BENDS AND CHANGES IN DIRECTION                G2417.1.4  (406.1.4)  Section  testing.  A  piping system
                                                                 shall be permitted to be tested as a complete unit or in sec-
         G2416.1 (405.1) General. Changes in direction of pipe shall  tions. A  valve in a line  shall not  be used as a bulkhead
         be permitted to be made by the use of fittings, factory bends  between gas in one section of the piping system and test
         or field bends.                                         medium  in  an  adjacent  section,  except  where  a  double
         G2416.2  (405.2)  Metallic  pipe.  Metallic  pipe  bends  shall  block and bleed valve system is installed. A valve shall not
         comply with the following:                              be  subjected  to  the  test  pressure  unless  it  can  be  deter-
                                                                 mined that the valve, including the valve-closing mecha-
           1. Bends shall be made only with bending tools and pro-  nism, is designed to safely withstand the test pressure.
              cedures intended for that purpose.
                                                                 G2417.1.5  (406.1.5)  Regulators  and  valve  assemblies.
           2. Bends shall be smooth and free from buckling, cracks  Regulator and valve assemblies fabricated independently
              or other evidence of mechanical damage.            of the piping system in which they are to be installed shall
           3. The longitudinal weld of the pipe shall be near the neu-  be permitted to be tested with inert gas or air at the time of
              tral axis of the bend.                             fabrication.
           4. Pipe shall not be bent through an arc of more than 90  G2417.1.6  (406.1.6)  Pipe  clearing.  Prior  to  testing,  the
              degrees (1.6 rad).                                 interior of the pipe shall be cleared of all foreign material.

         580                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®