FUEL GAS



               3. Listed and labeled appliance connectors in compliance     2. Rigid steel pipe connectors shall be permitted
                  with  ANSI  Z21.24/CSA  6.10  and  installed  in  accor-    to extend through openings in appliance hous-
                  dance with the manufacturer’s instructions and located      ings.
                  entirely in the same room as the appliance.               3. Fireplace  inserts  that  are  factory  equipped
               4. Listed and labeled quick-disconnect devices used in con-    with grommets, sleeves or other means of pro-
                  junction with listed and labeled appliance connectors.      tection  in  accordance  with  the  listing  of  the
               5. Listed and labeled convenience outlets used in conjunc-     appliance.
                  tion with listed and labeled appliance connectors.        4. Semirigid  tubing  and  listed  connectors  shall
               6. Listed  and  labeled  outdoor  appliance connectors  in     be permitted to extend through an opening in
                  compliance with ANSI Z21.75/CSA 6.27 and installed          an appliance housing, cabinet or casing where
                  in accordance with the manufacturer’s instructions.         the  tubing  or  connector  is  protected  against
                                                                              damage.
               7. Listed outdoor gas hose connectors in compliance with
                  ANSI Z21.54 used to connect portable outdoor appli-  G2422.1.2.4 (411.1.3.4) Shutoff valve. A shutoff valve
                  ances. The gas hose connection shall be made only in  not less than the nominal size of the connector shall be
                  the outdoor area where the appliance is used, and shall  installed  ahead  of  the  connector  in  accordance  with
                  be  to  the  gas  piping  supply  at  an  appliance  shutoff  Section G2420.5.
                  valve,  a  listed  quick-disconnect  device  or  listed  gas  G2422.1.3 (411.1.5) Connection of gas engine-powered
                  convenience outlet.                                air conditioners. Internal combustion engines shall not be
               G2422.1.1 (411.1.2) Protection from damage. Connec-   rigidly connected to the gas supply piping.
               tors  and  tubing  shall  be  installed  so  as  to  be  protected  G2422.1.4 (411.1.6) Unions. A union fitting shall be pro-
               against physical damage.                              vided  for  appliances  connected  by  rigid  metallic  pipe.
                                                                     Such unions shall be accessible and located within 6 feet
               G2422.1.2  (411.1.3)  Connector  installation.  Appliance
               fuel connectors shall be installed in accordance with the  (1829 mm) of the appliance.
               manufacturer’s  instructions  and  Sections  G2422.1.2.1  G2422.1.5 (411.1.4) Movable appliances. Where appli-
               through G2422.1.2.4.                                  ances are equipped with casters or are otherwise subject to
                  G2422.1.2.1  (411.1.3.1)  Maximum  length.  Connec-  periodic movement or relocation for purposes such as rou-
                  tors shall have an overall length not to exceed 6 feet  tine cleaning and maintenance, such appliances shall be
                  (1829 mm). Measurement shall be made along the cen-  connected  to  the  supply  system  piping  by  means  of  an
                  terline  of the connector.  Only one connector shall be  appliance  connector listed  as  complying  with  ANSI
                  used for each appliance.                           Z21.69/CSA  6.16  or  by  means  of  Item  1  of  Section
                                                                     G2422.1. Such flexible connectors shall be installed and
                    Exception: Rigid metallic piping used to connect an  protected against physical damage in accordance with the
                    appliance to the piping system shall be permitted to  manufacturer’s instructions.
                    have a total length greater than 6 feet (1829 mm),
                    provided that the connecting pipe is sized as part of  G2422.2  (411.3)  Suspended  low-intensity  infrared  tube
                    the piping system in accordance with Section G2413  heaters. Suspended low-intensity infrared tube heaters shall
                    and the location of the appliance shutoff valve com-  be connected to the building piping system with a connector
                    plies with Section G2420.5.                   listed for the application complying with ANSI Z21.24/CGA
                                                                  6.10. The connector shall be installed as specified by the tube
                  G2422.1.2.2  (411.1.3.2)  Minimum  size.  Connectors  heater manufacturer’s instructions.
                  shall have the capacity for the total demand of the con-
                  nected appliance.
                  G2422.1.2.3  (411.1.3.3)  Prohibited  locations  and          SECTION G2423 (413)
                  penetrations.  Connectors  shall  not  be  concealed  COMPRESSED NATURAL GAS MOTOR
                  within,  or  extended  through,  walls,  floors,  partitions,  VEHICLE FUEL-DISPENSING FACILITIES
                  ceilings or appliance housings.                 G2423.1  (413.1)  General.  Motor  fuel-dispensing  facilities
                    Exceptions:                                   for CNG fuel shall be in accordance with Section 413 of the
                                                                  International Fuel Gas Code.
                       1. Connectors  constructed  of  materials  allowed
                         for piping systems in accordance with Section
                         G2414  shall  be  permitted  to  pass  through         SECTION G2424 (415)
                         walls,  floors,  partitions  and  ceilings  where  PIPING SUPPORT INTERVALS
                         inst          accordan         Section
                         G2420.5.2 or G2420.5.3.                  G2424.1 (415.1) Interval of support. Piping shall be sup-
                                                                  ported  at  intervals  not  exceeding  the  spacing  specified  in
                                                                  Table  G2424.1.  Spacing  of  supports  for  CSST  shall  be  in
                                                                  accordance with the CSST manufacturer’s instructions.