FUEL GAS



           Appliance shutoff valves located in the firebox of a fire-  6. A tee fitting with one opening capped or plugged shall
           place shall be installed in accordance with the appliance  be installed not less than 10 pipe diameters downstream
           manufacturer’s instructions.                            of  the  MP  regulator  outlet.  Such  tee  fitting  shall  be
           G2420.5.2 (409.5.2) Vented decorative appliances and    positioned to allow connection of a pressure-measuring
           room heaters. Shutoff valves for vented decorative appli-  instrument. The tee fitting is not required where the MP
           ances, room heaters and decorative appliances for installa-  regulator  serves  an  appliance  that  has  a  pressure  test
           tion in vented fireplaces shall be permitted to be installed  port on the gas control inlet side and the appliance is
           in an area remote from the appliances where such valves  located in the same room as the MP regulator.
           are provided with ready access. Such valves shall be per-  7. Where  connected  to  rigid  piping,  a  union  shall  be
           manently identified and shall not serve another appliance.  installed within 1 foot (304 mm) of either side of the
           The piping from the shutoff valve to within 6 feet (1829  MP regulator.
           mm)  of  the  appliance  shall  be  designed,  sized  and
           installed  in  accordance  with  Sections  G2412  through  G2421.3 (410.3) Venting of regulators. Pressure regulators
           G2419.                                             that require a vent shall be vented directly to the outdoors.
                                                              The  vent  shall  be  designed  to  prevent  the  entry  of  insects,
           G2420.5.3  (409.5.3)  Located  at  manifold.  Where  the  water and foreign objects.
           appliance  shutoff  valve  is  installed  at  a  manifold,  such
           shutoff valve shall be located within 50 feet (15 240 mm)  Exception: A vent to the outdoors is not required for reg-
           of the appliance served and shall be readily accessible and  ulators equipped with and labeled for utilization with an
           permanently identified. The piping from the manifold to  approved vent-limiting device installed in accordance with
           within  6  feet  (1829  mm)  of  the  appliance  shall  be  the manufacturer’s instructions.
           designed, sized and installed in accordance with Sections  G2421.3.1 (410.3.1) Vent piping. Vent piping for relief
           G2412 through G2419.                                  vents and breather vents shall be constructed of materials
         G2420.6 (409.7) Shutoff valves in tubing systems. Shutoff  allowed for gas piping in accordance with Section G2414.
         valves  installed  in  tubing  systems  shall  be  rigidly  and  Vent piping shall be not smaller than the vent connection
         securely supported independently of the tubing.         on  the  pressure-regulating  device.  Vent  piping  serving
                                                                 relief vents and combination relief and breather vents shall
                                                                 be run independently to the outdoors and shall serve only a
                       SECTION G2421 (410)                       single device vent. Vent piping serving only breather vents
                         FLOW CONTROLS                           is  permitted  to  be  connected  in  a  manifold  arrangement
                                                                 where sized in accordance with an approved design that
         G2421.1 (410.1) Pressure regulators. A line pressure regu-
         lator  shall  be  installed  where  the  appliance  is  designed  to  minimizes backpressure in the event of diaphragm rupture.
         operate at a lower pressure than the supply pressure. Line gas  Regulator vent piping shall not exceed the length specified
         pressure regulators shall be listed as complying with ANSI  in the regulator manufacturer’s instructions.
         Z21.80/CSA 6.22. Access shall be provided to pressure regu-  G2421.4  (410.4)  Excess  flow  valves.  Where  automatic
         lators. Pressure regulators shall be protected from physical  excess flow valves are installed, they shall be listed in accor-
         damage. Regulators installed on the exterior of the building  dance with ANSI Z21.93/CSA 6.30 and shall be sized and
         shall be approved for outdoor installation.          installed in accordance with the manufacturer’s instructions.
         G2421.2  (410.2)  MP  regulators.  MP  pressure regulators  G2421.5  (410.5)  Flashback  arrestor  check  valve.   Where
         shall comply with the following:                     fuel  gas is  used  with oxygen  in  any hot  work  operation,  a
           1. The MP regulator shall be approved and shall be suit-  listed  protective  device  that  serves  as  a  combination  flash-
              able for the inlet and outlet gas pressures for the appli-  back arrestor and backflow check valve shall be installed at
              cation.                                         an approved location on both the fuel gas and oxygen supply
                                                              lines.  Where  the  pressure  of  the  piped  fuel  gas  supply  is
           2. The MP regulator shall maintain a reduced outlet pres-
              sure under lock-up (no-flow) conditions.        insufficient  to  ensure  such  safe  operation,  approved  equip-
                                                              ment shall be installed between the gas meter and the appli-
           3. The capacity of the MP regulator, determined by pub-  ance that increases pressure to the level required for such safe
              lished ratings of its manufacturer, shall be adequate to  operation.
              supply the appliances served.
           4. The  MP  pressure regulator  shall  be  provided  with
              access. Where located indoors, the regulator shall be         SECTION G2422 (411)
              vented to the outdoors or shall be equipped with a leak-   APPLIANCE CONNECTIONS
              limiting device, in either case complying with Section  G2422.1  (411.1)  Connecting  appliances.  Appliances  shall
              G2421.3.                                        be connected to the piping system by one of the following:
           5. A tee fitting with one opening capped or plugged shall  1. Rigid metallic pipe and fittings.
              be installed between the MP regulator and its upstream
              shutoff  valve.  Such  tee  fitting  shall  be  positioned  to  2. Corrugated  stainless  steel  tubing  (CSST)  where
              allow  connection  of  a  pressure-measuring  instrument  installed in accordance with the manufacturer’s instruc-
              and to serve as a sediment trap.                     tions.

         584                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®