FUEL GAS



                      TABLE G2417.7.1.1 (406.7.1.1)                2. The piping being purged is constructed entirely from
                      SIZE AND LENGTH OF PIPING                      pipe or tubing not meeting the size and length crite-
               NOMINAL PIPE SIZE       LENGTH OF PIPING              ria of Table G2417.7.1.1.
                  (inches) a                (feet)
            1
         ≥ 2 / < 3                          > 50                   G2417.7.2.1 (406.7.2.1) Purging procedure. The pip-
             2
         ≥ 3 < 4                            > 30                   ing system shall be purged in accordance with one or
                                                                   more of the following:
         ≥ 4 < 6                            > 15
         ≥ 6 < 8                            > 10                     1. The piping shall be purged with fuel gas and shall
                                                                        discharge to the outdoors.
         ≥ 8                              Any length
                                                                     2. The piping shall be purged with fuel gas and shall
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
                                                                        discharge to the indoors or outdoors through an
         a. CSST EHD size of 62 is equivalent to nominal 2-inch pipe or tubing size.  appliance  burner  not  located  in  a  combustion
              G2417.7.1.2 (406.7.1.2) Placing in operation. Where       chamber.  Such  burner  shall  be  provided  with  a
              gas  piping  containing  air  and  meeting  the  criteria  of  continuous source of ignition.
              Table G2417.7.1.1 is placed in operation, the air in the  3. The piping shall be purged with fuel gas and shall
              piping  shall  first  be  displaced  with  an  inert  gas.  The  discharge  to  the  indoors  or  outdoors  through  a
              inert gas shall then be displaced with fuel gas in accor-  burner  that  has  a  continuous  source  of  ignition
              dance with Section G2417.7.1.3.                           and that is designed for such purpose.
              G2417.7.1.3  (406.7.1.3)  Outdoor  discharge  of       4. The piping shall be purged with fuel gas that is
              purged gases. The open end of a piping system being       discharged  to  the  indoors  or  outdoors,  and  the
              pressure vented or purged shall discharge directly to an  point  of  discharge  shall  be  monitored  with  a
              outdoor location. Purging operations shall comply will    listed  combustible  gas  detector  in  accordance
              all of the following requirements:                        with  Section  G2417.7.2.2.  Purging  shall  be
                                                                        stopped when fuel gas is detected.
                1. The point of discharge shall be controlled with a
                   shutoff valve.                                    5. The piping shall be purged by the gas supplier in
                                                                        accordance with written procedures.
                2. The point of discharge shall be located not less
                   than 10 feet (3048 mm) from sources of ignition,  G2417.7.2.2  (406.7.2.2)  Combustible  gas  detector.
                                                                   Combustible gas detectors shall be listed and shall be
                   not  less  than  10  feet  (3048  mm)  from  building
                   openings  and  not  less  than  25  feet  (7620  mm)  calibrated  or  tested  in  accordance  with  the  manufac-
                                                                   turer’s instructions. Combustible gas detectors shall be
                   from mechanical air intake openings.
                                                                   capable of indicating the presence of fuel gas.
                3. During  discharge,  the  open  point  of  discharge  G2417.7.3  (406.7.3)  Purging  appliances  and  equip-
                   shall  be  continuously  attended  and  monitored  ment. After the piping system has been placed in opera-
                   with  a  combustible  gas  indicator  that  complies  tion,  appliances  and  equipment  shall  be  purged  before
                   with Section G2417.7.1.4.                     being placed into operation.
                4. Purging operations introducing fuel gas shall be
                   stopped when 90 percent fuel gas by volume is
                   detected within the pipe.                                SECTION G2418 (407)
                                                                              PIPING SUPPORT
                5. Persons  not  involved  in  the  purging  operations  G2418.1 (407.1) General. Piping shall be provided with sup-
                   shall be evacuated from all areas within 10 feet  port in accordance with Section G2418.2.
                   (3048 mm) of the point of discharge.
                                                              G2418.2  (407.2)  Design  and  installation.  Piping  shall  be
              G2417.7.1.4  (406.7.1.4)  Combustible  gas  indicator.  supported  with  metal  pipe  hooks,  metal  pipe  straps,  metal
              Combustible gas indicators shall be listed and shall be  bands,  metal  brackets,  metal  hangers  or  building  structural
              calibrated  in  accordance  with  the  manufacturer’s  components  suitable  for  the  size  of  piping,  of  adequate
              instructions. Combustible gas indicators shall numeri-  strength and quality, and located at intervals so as to prevent
              cally display a volume scale from zero percent to 100  or damp out excessive vibration. Piping shall be anchored to
              percent in 1-percent or smaller increments.     prevent undue strains on connected appliances and shall not
           G2417.7.2  (406.7.2)  Piping  systems  allowed  to  be  be supported by other piping. Pipe hangers and supports shall
                                                              conform  to  the  requirements  of  MSS  SP-58  and  shall  be
           purged indoors or outdoors. The purging of piping sys-  spaced in accordance with Section G2424. Supports, hangers
           tems shall be in accordance with the provisions of Section
           G2417.7.2.1  where  the  piping system  meets  both  of  the  and anchors shall be installed so as not to interfere with the
           following:                                         free  expansion  and  contraction  of  the  piping  between
                                                              anchors. The components of the supporting equipment shall
              1. The design operating gas pressure is 2 psig (13.79  be designed and installed so that they will not be disengaged
                kPa) or less.                                 by movement of the supported piping.