FUEL GAS



                         TABLE G2424.1 (415.1)                   both the connector and the flue. Listed direct connection
                         SUPPORT OF PIPING                       devices shall be installed in accordance with their listing.
           STEEL PIPE,             NOMINAL SIZE
           NOMINAL SIZE  SPACING OF   OF TUBING  SPACING OF   G2425.8 (501.8) Appliances not required to be vented. The
                        SUPPORTS
                                                 SUPPORTS
             OF PIPE      (feet)   SMOOTH-WALL     (feet)     following appliances shall not be required to be vented:
             (inches)                (inch O.D.)
         1 / 2              6           1 / 2       4            1. Ranges.
         3 / or 1           8         5 / or / 4    6            2. Built-in domestic cooking units listed and marked for
                                          3
          4
                                       8
          1
         1 / or larger     10         7 / or 1      8              optional venting.
           4
                                       8
         (horizontal)               (horizontal)                 3. Hot plates and laundry stoves.
          1
         1 / or larger  Every floor   1 or larger  Every floor   4. Type 1 clothes dryers (Type 1 clothes dryers shall be
           4
         (vertical)       level      (vertical)    level           exhausted in accordance with the requirements of Sec-
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.              tion G2439).
                                                                 5. Refrigerators.
                       SECTION G2425 (501)                       6. Counter appliances.
                             GENERAL                             7. Room heaters listed for unvented use.
         G2425.1 (501.1) Scope. This section shall govern the instal-  Where  the  appliances  listed  in  Items  5  through  7  are
         lation,  maintenance,  repair  and  approval  of  factory-built  installed so that the aggregate input rating exceeds 20 Btu per
         chimneys, chimney liners, vents and connectors and the utili-  hour per cubic foot  (207 W/m )  of  volume of the room  or
                                                                                        3
         zation of masonry chimneys serving gas-fired appliances.  space  in  which  such  appliances  are  installed,  one  or  more
         G2425.2  (501.2) General. Every appliance shall discharge  shall  be  provided  with  venting  systems  or  other  approved
         the products of combustion to the outdoors, except for appli-  means  for  conveying  the  vent  gases  to  the  outdoor  atmo-
         ances exempted by Section G2425.8.                   sphere  so  that  the  aggregate  input  rating  of  the  remaining
                                                              unvented appliances  does  not  exceed  20  Btu  per  hour  per
         G2425.3  (501.3)  Masonry  chimneys.  Masonry chimneys  cubic foot (207 W/m ). Where the room or space in which the
                                                                               3
         shall be constructed in accordance with Section G2427.5 and  appliance is installed is directly connected to another room or
         Chapter 10.                                          space by a doorway, archway or other opening of comparable
                                                              size that cannot be closed, the volume of such adjacent room
         G2425.4 (501.4) Minimum size of chimney or vent. Chim-
         neys  and  vents  shall  be  sized  in  accordance  with  Sections  or space shall be permitted to be included in the calculations.
         G2427 and G2428.                                     G2425.9 (501.9) Chimney entrance. Connectors shall con-
         G2425.5  (501.5)  Abandoned  inlet  openings.  Abandoned  nect to a masonry chimney flue at a point not less than 12
         inlet openings in chimneys and vents shall be closed by an  inches (305 mm) above the lowest portion of the interior of
         approved method.                                     the chimney flue.
                                                              G2425.10  (501.10)  Connections  to  exhauster.  Appliance
         G2425.6  (501.6)  Positive  pressure.  Where  an  appliance
         equipped  with  a  mechanical  forced  draft  system  creates  a  connections  to  a  chimney  or  vent  equipped  with  a  power
         positive pressure in the venting system, the venting system  exhauster  shall  be  made  on  the inlet  side  of  the exhauster.
         shall be designed for positive pressure applications.  Joints on the positive pressure side of the exhauster shall be
                                                              sealed to prevent flue-gas leakage as specified by the manu-
         G2425.7  (501.7)  Connection  to  fireplace.  Connection  of  facturer’s installation instructions for the exhauster.
         appliances  to  chimney  flues  serving  fireplaces  shall  be  in
         accordance with Sections G2425.7.1 through G2425.7.3.  G2425.11 (501.11) Masonry chimneys. Masonry chimneys
                                                              utilized to vent appliances shall be located, constructed and
           G2425.7.1 (501.7.1) Closure and access. A noncombusti-  sized as specified in the manufacturer’s installation instruc-
           ble seal shall be provided below the point of connection to  tions for the appliances being vented and Section G2427.
           prevent entry of room air into the flue. Means shall be pro-
           vided for access to the flue for inspection and cleaning.  G2425.12  (501.12)  Residential  and  low-heat  appliances
                                                              flue lining systems. Flue lining systems for use with residen-
           G2425.7.2  (501.7.2)  Connection  to  factory-built  fire-  tial-type and low-heat appliances shall be limited to the fol-
           place flue. An appliance shall not be connected to a flue  lowing:
           serving  a  factory-built fireplace  unless  the  appliance  is
           specifically  listed  for  such  installation.  The  connection  1. Clay  flue lining  complying  with  the  requirements  of
           shall be made in accordance with the appliance manufac-  ASTM  C315  or  equivalent.  Clay  flue lining  shall  be
           turer’s installation instructions.                      installed in accordance with Chapter 10.
           G2425.7.3  (501.7.3)  Connection  to  masonry  fireplace  2. Listed  chimney  lining  systems  complying  with  UL
           flue. A connector shall extend from the appliance to the  1777.
           flue serving a masonry fireplace such that the flue gases  3. Other  approved  materials  that  will  resist,  without
           are exhausted directly into the flue. The connector shall be  cracking,  softening  or  corrosion,  flue gases  and  con-
           accessible  or  removable  for  inspection  and  cleaning  of  densate at temperatures up to 1,800ºF (982ºC).



         586                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.