Page 604 - 2018_IRC
P. 604

FUEL GAS



             G2415.10  (404.10)  Isolation.  Metallic  piping  and  metallic  listed  for  installation  beneath  buildings,  or  other  approved
             tubing that conveys fuel gas from an LP-gas storage container  conduit  material  designed  to  withstand  the  superimposed
             shall be provided with an approved dielectric fitting to elec-  loads. The conduit shall be protected from corrosion in accor-
             trically isolate  the underground portion of the pipe or tube  dance with Section G2415.11 and shall be installed in accor-
             from the above-ground portion that enters a building. Such  dance with Section G2415.14.1 or G2415.14.2.
             dielectric fitting shall be installed above ground, outdoors.  G2415.14.1 (404.14.1) Conduit with one end terminat-
             G2415.11 (404.11) Protection against corrosion. Steel pipe  ing outdoors. The conduit shall extend into an occupiable
             or tubing exposed to corrosive action, such as soil condition  portion of the building and, at the point where the conduit
             or moisture, shall be protected in accordance with Sections  terminates in the building, the space between the conduit
             G2415.11.1 through G2415.11.5.                          and the gas piping shall be sealed to prevent the possible
               G2415.11.1  (404.11.1)  Galvanizing.  Zinc  coating  shall  entrance of any gas leakage. The conduit shall extend not
               not  be  deemed  adequate  protection  for  underground  gas  less  than  2  inches (51  mm)  beyond the  point  where  the
               piping.                                               pipe  emerges  from  the  floor.  Where  the  end  sealing  is
                                                                     capable of withstanding the full pressure of the gas pipe,
               G2415.11.2  (404.11.2)  Protection  methods.  Under-  the conduit shall be designed for the same pressure as the
               ground piping shall comply with one or more of the fol-  pipe. Such conduit shall extend not less than 4 inches (102
               lowing:                                               mm) outside the building, shall be vented above grade to
                  1. The  piping  shall  be  made  of  corrosion-resistant  the  outdoors  and  shall  be  installed  so  as  to  prevent  the
                    material  that  is  suitable  for  the  environment  in  entrance of water and insects.
                    which it will be installed.                      G2415.14.2  (404.14.2)  Conduit  with  both  ends  termi-
                  2. Pipe shall have a factory-applied, electrically-insu-  nating indoors. Where the conduit originates and termi-
                    lating coating. Fittings and joints between sections  nates within the same building, the conduit shall originate
                    of coated pipe shall be coated in accordance with the  and terminate in an accessible portion of the building and
                    coating manufacturer’s instructions.             shall not be sealed. The conduit shall extend not less than
                                                                     2  inches  (51  mm)  beyond  the  point  where  the  pipe
                  3. The piping shall have a cathodic protection system  emerges from the floor.
                    installed  and  the  system  shall  be  monitored  and
                    maintained  in  accordance  with  an  approved  pro-  G2415.15 (404.15) Outlet closures. Gas outlets that do not
                    gram.                                         connect to appliances shall be capped gas tight.
               G2415.11.3 (404.11.3) Dissimilar metals. Where dissimi-  Exception: Listed and labeled flush-mounted-type quick-
               lar metals are joined underground, an insulating coupling  disconnect devices and listed and labeled gas convenience
               or fitting shall be used.                             outlets shall be installed in accordance with the manufac-
                                                                     turer’s instructions.
               G2415.11.4 (404.11.4) Protection of  risers. Steel risers
               connected to plastic piping shall be cathodically protected  G2415.16 (404.16) Location of outlets. The unthreaded por-
               by means of a welded anode, except where such risers are  tion of piping outlets shall extend not less than l inch (25 mm)
               anodeless risers.                                  through  finished  ceilings  and  walls  and  where  extending
                                                                  through floors or outdoor patios and slabs, shall be not less
               G2415.11.5  (404.11.5)  Prohibited  use.  Uncoated
               threaded or socket-welded joints shall not be used in pip-  than 2 inches (51 mm) above them. The outlet fitting or pip-
                                                                  ing shall be securely supported. Outlets shall not be placed
               ing in contact with soil or where internal or external crev-  behind doors. Outlets shall be located in the room or space
               ice corrosion is known to occur.
                                                                 where the appliance is installed.
             G2415.12  (404.12)  Minimum  burial  depth.  Underground
             piping systems  shall  be  installed  a  minimum  depth  of  12  Exception: Listed and labeled flush-mounted-type quick-
             inches (305 mm) below grade, except as provided for in Sec-  disconnect devices and listed and labeled gas convenience
             tion G2415.12.1.                                        outlets shall be installed in accordance with the manufac-
                                                                     turer’s instructions.
               G2415.12.1  (404.12.1)  Individual  outdoor  appliances.  G2415.17 (404.17) Plastic  pipe.  The installation of  plastic
               Individual lines to outdoor lights, grills and other  appli-  pipe  shall  comply  with  Sections  G2415.17.1  through
               ances shall be installed not less than 8 inches (203 mm)
               below  finished  grade,  provided  that  such  installation  is  G2415.17.3.
               approved  and  is installed in  locations  not  susceptible  to  G2415.17.1 (404.17.1) Limitations. Plastic pipe shall be
               physical damage.                                      installed outdoors underground only. Plastic pipe shall not
                                                                     be used within or under any building or slab or be operated
             G2415.13 (404.13) Trenches. The trench shall be graded so
             that the pipe has a firm, substantially continuous bearing on  at pressures greater than 100 psig (689 kPa) for natural gas
             the bottom of the trench.                               or 30 psig (207 kPa) for LP-gas.
                                                                       Exceptions:
             G2415.14 (404.14) Piping underground beneath buildings.
             Piping installed underground beneath buildings is prohibited  1. Plastic pipe shall be permitted to terminate above
             except where the piping is encased in a conduit of wrought     ground  outside  of  buildings  where  installed  in
             iron, plastic pipe, steel pipe, a piping or encasement system  premanufactured anodeless risers or service head


             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               579
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   599   600   601   602   603   604   605   606   607   608   609