Page 694 - 2018_IRC
P. 694

SANITARY DRAINAGE


               P3005.1.1  Horizontal  to  vertical  (multiple  connection  P3005.2  Cleanouts  required.  Cleanouts  shall  be  provided
               fittings). Double fittings such as double sanitary tees and  for  drainage  piping  in  accordance  with  Sections  P3005.2.1
               tee-wyes  or  approved  multiple  connection  fittings  and  through P3005.2.11.
               back-to-back fixture arrangements that connect two or more  P3005.2.1 Horizontal drains and building drains. Hori-
               branches at the same level shall be permitted as long as  zontal  drainage  pipes  in  buildings  shall  have  cleanouts
               directly opposing connections are the same size and the dis-  located at intervals of not more than 100 feet (30 480 mm).
               charge into directly opposing connections is from similar  Building drains shall have cleanouts located at intervals of
               fixture types or fixture groups. Double sanitary tee patterns  not more than 100 feet (30 480 mm) except where man-
               shall not receive the discharge of back-to-back water closets  holes are used instead of cleanouts, the manholes shall be
               and fixtures or appliances with pumping action discharge.  located at intervals of not more than 400 feet (122 m). The
                  Exception:  Back-to-back  water  closet  connections  to  interval length shall be measured from the cleanout or man-
                  double  sanitary  tee  patterns  shall  be  permitted  where  hole opening, along the developed length of the piping to
                  the horizontal developed length between the outlet of  the next drainage fitting providing access for cleaning, the
                  the water closet and the connection to the double sani-  end of the horizontal drain or the end of the building drain.
                  tary tee is 18 inches (457 mm) or greater.           Exception:  Horizontal  fixture  drain  piping  serving  a
               P3005.1.2 Heel- or side-inlet quarter bends, drainage.  nonremovable trap shall not be required to have a clea-
               Heel-inlet quarter bends shall be an acceptable means of  nout for the section of piping between the trap and the
               connection, except where the quarter bends serves a water  vent connection for such trap.
               closet. A low-heel inlet shall not be used as a wet-vented  P3005.2.2 Building sewers. Building sewers smaller than
               connection. Side-inlet quarter bends shall be an acceptable  8 inches (203 mm) shall have cleanouts located at intervals
               means of connection for both drainage, wet venting and  of not more than 100 feet (30 480 mm). Building sewers 8
               stack venting arrangements.                           inches (203 mm) and larger shall have a manhole located
               P3005.1.3  Heel-  or  side-inlet  quarter  bends,  venting.  not more than 200 feet (60 960 mm) from the junction of
               Heel-inlet or side-inlet quarter bends, or any arrangement  the building drain and building sewer and at intervals of
               of  pipe  and  fittings  producing  a  similar  effect,  shall  be  not more than 400 feet (122 m). The interval length shall
               acceptable as a dry vent where the inlet is placed in a verti-  be measured from the cleanout or manhole opening, along
               cal position. The inlet is permitted to be placed in a hori-  the developed length of the piping to the next drainage fit-
               zontal position only where the entire fitting is part of a dry  ting providing access for cleaning, a manhole or the end of
               vent arrangement.                                     the building sewer.
               P3005.1.4 Water closet connection between flange and  P3005.2.3 Building drain and building sewer junction.
               pipe.  One-quarter  bends  3  inches  (76  mm)  in  diameter  The junction of the building drain and the building sewer
               shall be acceptable for water closet or similar connections,  shall be served by a cleanout that is located at the junction
               provided  that  a  4-inch  by  3-inch  (102  mm  by  76  mm)  or within 10 feet (3048 mm) developed length of piping
               flange is installed to receive the closet fixture horn. Alter-  upstream of the junction. For the requirements of this sec-
               nately, a 4-inch by 3-inch (102 mm by 76 mm) elbow shall  tion, removal of a water closet shall not be required to pro-
               be acceptable with a 4-inch (102 mm) flange.          vide cleanout access.
               P3005.1.5 Provisions for future fixtures. Where drain-  P3005.2.4  Changes  of  direction.  Where  a  horizontal
               age has been roughed-in for future fixtures, the drainage  drainage pipe, a building drain or a building sewer has a
               unit  values  of  the  future  fixtures  shall  be  considered  in  change of horizontal direction greater than 45 degrees (0.79
               determining the required drain sizes. Such future installa-  rad), a cleanout shall be installed at the change of direction.
               tions  shall  be  terminated  with  an  accessible  permanent  Where more than one change of horizontal direction greater
               plug or cap fitting.                                  than 45 degrees (0.79 rad) occurs within 40 feet (12 192
               P3005.1.6 Drainage piping size reduction in the direc-  mm) of developed length of piping, the cleanout installed
               tion of flow. The size of the drainage piping shall not be  for the first change of direction shall serve as the cleanout
               reduced in the direction of the flow. The following shall  for all changes in direction within that 40 feet (12 192 mm)
               not be considered a reduction in size in the direction of  of developed length of piping.
               flow:                                                 P3005.2.5 Cleanout size. Cleanouts shall be the same size
                  1. A 4-inch by 3-inch (102 mm by 76 mm) water closet  as the piping served by the cleanout, except cleanouts for
                    flange.                                          piping larger than 4 inches (102 mm) need not be larger
                                                                     than 4 inches (102 mm).
                  2. A  water  closet  bend  fitting  having  a  4-inch  (102
                    mm) inlet and a 3-inch (76 mm) outlet provided that  Exceptions:
                    the 4-inch leg of the fitting is upright and below, but  1. A  removable  P-trap  with  slip-  or  ground-joint
                    not  necessarily  directly  connected  to,  the  water  connections can serve as a cleanout for drain pip-
                    closet flange.                                          ing that is one size larger than the P-trap size.
                  3. An offset closet flange.                            2. Cleanouts  located  on  stacks  can  be  one  size
                                                                            smaller than the stack size.




             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               669
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   689   690   691   692   693   694   695   696   697   698   699