Page 726 - 2018_IRC
P. 726

CHAPTER 36

                                                        SERVICES




             ICC user note:
                About this chapter: Chapter 36 is the first of the logical order of chapters that mimics the normal sequence of dwelling construction. The first
                step in dwelling wiring is typically the sizing, design and installation of the service that is the source of power for the building. This chapter
                addresses the sizing of services, service conductor sizing and installation, system grounding and bonding, overcurrent protection, disconnect-
                ing means and the grounding electrode system.
                This chapter requires  services  to be  properly sized to serve  the  load. This  is intended to  prevent overloading and to provide the utility
                expected by the occupants. This chapter is also intended to protect occupants and the building from fire and protect the occupants from elec-
                trical shock hazards associated with service conductors and equipment.



                              SECTION E3601                       E3601.7  Maximum  number  of  disconnects.  The  service
                           GENERAL SERVICES                       disconnecting  means  shall  consist  of  not  more  than  six
             E3601.1 Scope. This chapter covers service conductors and  switches or six sets of circuit breakers mounted in a single
             equipment for the control and protection of services and their  enclosure or in a group of separate enclosures. [230.71(A)]
             installation requirements. (230.1)
             E3601.2 Number  of services. One- and two-family dwell-               SECTION E3602
             ings shall be supplied by only one service. (230.2)             SERVICE SIZE AND RATING
             E3601.3  One  building  or  other structure not  to  be  sup-  E3602.1 Ampacity of ungrounded conductors. Ungrounded
             plied  through  another.  Service  conductors  supplying  a  service conductors shall have an ampacity of not less than the
             building or other structure shall not pass through the interior  load  served.  For  one-family  dwellings,  the  ampacity  of  the
             of another building or other structure. (230.3)      ungrounded conductors shall be not less than 100 amperes, 3
             E3601.4 Other conductors in raceway or cable. Conduc-  wire. For all other installations, the ampacity of the ungrounded
             tors other than service conductors shall not be installed in the  conductors  shall  be  not  less  than  60  amperes.  [230.42(B),
             same service raceway or service cable in which the service  230.79(C) & (D)]
             conductors are installed. (230.7)                    E3602.2  Service  load.  The  minimum  load  for  ungrounded
               Exceptions:                                        service conductors and service devices that serve 100 percent
                                                                  of  the  dwelling  unit  load  shall  be  computed  in  accordance
                  1. Grounding  electrode  conductors  or  supply  side  with Table E3602.2. Ungrounded service conductors and ser-
                    bonding  jumpers  or  conductors  shall  be  permitted  vice devices that serve less than 100 percent of the dwelling
                    within service raceways.
                                                                  unit load shall be computed as required for feeders in accor-
                  2. Load management control conductors having over-  dance with Chapter 37. [220.82(A)]
                    current protection shall be permitted within service  E3602.2.1 Services under 100 amperes. Services that are
                    raceways.
                                                                     not  required  to  be  100  amperes  shall  be  sized  in  accor-
             E3601.5 Raceway seal. Where a service raceway enters from  dance with Chapter 37. [230.42(A), (B), and (C)].
             an  underground  distribution  system,  it  shall  be  sealed  in
             accordance with Section E3803.6. (230.8)
             E3601.6 Service disconnect required. Means shall be pro-
             vided  to  disconnect  all  conductors  in  a  building  or  other
             structure from the service entrance conductors. (230.70)
               E3601.6.1  Marking  of  service  equipment  and  discon-
               nects. Service disconnects shall be permanently marked as
               a service disconnect. [230.70(B)]
               E3601.6.2 Service disconnect location. The service discon-
               necting means shall be installed at a readily accessible loca-
               tion either outside of a building or inside nearest the point of
               entrance of the service conductors.  Service  disconnecting
               means shall not be installed in bathrooms. Each occupant
               shall have access to the disconnect serving the dwelling unit
               in which they reside. [230.70(A)(1)(2), 230.72(C)]




             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               701
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   721   722   723   724   725   726   727   728   729   730   731