Page 728 - 2018_IRC
P. 728

SERVICES



                  the overload protection. The sum of the ratings of the  E3603.5 Temperature limitations. Except where the equip-
                  circuit breakers or fuses shall be permitted to exceed  ment  is  marked  otherwise,  conductor  ampacities  used  in
                  the ampacity of the service conductors, provided that  determining equipment termination provisions shall be based
                  the calculated load does not exceed the ampacity of the  on Table E3705.1. [110.14(C)(1)]
                  service conductors. [230.90(A) Exception No. 3]
               E3603.3.2  Not  in  grounded  conductor.  Overcurrent
               devices shall not be connected in series with a grounded            SECTION E3604
               service conductor except where a circuit breaker is used  OVERHEAD SERVICE AND SERVICE-
               that  simultaneously  opens  all  conductors  of  the  circuit.  ENTRANCE CONDUCTOR INSTALLATION
               [230.90(B)]                                        E3604.1  Clearances  on  buildings.  Open  conductors  and
               E3603.3.3 Location. The service overcurrent device shall  multiconductor  cables  without  an  overall  outer  jacket  shall
               be an integral part of the service disconnecting means or  have a clearance of not less than 3 feet (914 mm) from the
               shall be located immediately adjacent thereto. Where fuses  sides of doors, porches, decks, stairs, ladders, fire escapes and
               are used as the service overcurrent device, the disconnect-  balconies,  and  from  the  sides  and  bottom  of  windows  that
               ing means shall be located on the supply side of the fuses.  open. See Figure E3604.1. [230.9(A)]
               (230.91)                                           E3604.2 Vertical clearances. Overhead service conductors
             E3603.4 Grounding electrode conductor size. The grounding  shall not have ready access and shall comply with Sections
             electrode conductors shall be sized based on the size of the ser-  E3604.2.1 and E3604.2.2. (230.24)
             vice entrance conductors as required in Table E3603.4. (250.66)  E3604.2.1 Above roofs. Conductors shall have a vertical
                                TABLE E3603.4                        clearance of not less than 8 feet (2438 mm) above the roof
                 GROUNDING ELECTRODE CONDUCTOR SIZE a, b, c, d, e, f  surface. The vertical clearance above the roof level shall
                SIZE OF LARGEST UNGROUNDED                           be maintained for a distance of not less than 3 feet (914
                 SERVICE-ENTRANCE CONDUCTOR  SIZE OF GROUNDING       mm) in all directions from the edge of the roof. See Figure
               OR EQUIVALENT AREA FOR PARALLEL  ELECTRODE CONDUCTOR  E3604.2.1. [230.24(A)]
                                                 (AWG/kcmil)
                   CONDUCTORS (AWG/kcmil)
                               Aluminum or           Aluminum or       Exceptions:
                  Copper        copper-clad  Copper  copper-clad         1. Conductors above a roof surface subject to pedes-
                                aluminum              aluminum
             2 or smaller      1/0 or smaller  8         6                  trian traffic shall have a vertical clearance from
                                                                            the  roof  surface  in  accordance  with  Section
             1 or 1/0           2/0 or 3/0     6         4                  E3604.2.2. [230.24(A) Exception No. 1]
             2/0 or 3/0         4/0 or 250     4         2               2. Where the roof has a slope of 4 inches (102 mm)
             Over 3/0           Over 250       2        1  /  0             in 12 inches (305 mm), or greater, the minimum
               through 350     through 500                                  clearance shall be 3 feet (914 mm). [230.24(A)
             Over 350           Over 500      1/0       3/0                 Exception No. 2]
               through 600     through 900
                                                                         3. The  minimum  clearance  above  only  the  over-
             a. If multiple sets of service-entrance conductors connect directly to a service  hanging portion of the roof shall not be less than
               drop,  set  of  overhead  service  conductors,  set  of  underground  service  18 inches (457 mm) where not more than 6 feet
               conductors, or service lateral, the equivalent size of the largest service-
               entrance conductor shall be determined by the largest sum of the areas of the  (1829 mm) of overhead service conductor length
               corresponding conductors of each set. (Table 250.66)         passes over 4 feet (1219 mm) or less of roof sur-
             b. Where there are no service-entrance conductors, the grounding electrode  face measured horizontally and such conductors
               conductor size shall be determined by the equivalent size of the largest  are terminated at a through-the-roof raceway or
               service-entrance  conductor  required  for  the  load  to  be  served.  (Table
               250.66)                                                      approved support. [230.24(A) Exception No. 3]
             c. Where  protected  by  a  ferrous  metal  raceway,  grounding  electrode  4. The  requirement  for  maintaining  the  vertical
               conductors  shall  be  electrically  bonded  to  the  ferrous  metal  raceway  at
               both ends. [250.64(E)(1)]                                    clearance for a distance of 3 feet (914 mm) from
             d. An 8 AWG grounding electrode conductor shall be protected with rigid  the edge of the roof shall not apply to the final
               metal conduit, intermediate metal conduit, rigid polyvinyl chloride (Type  conductor span where the service drop is attached
               PVC)  nonmetallic  conduit,  rigid  thermosetting  resin  (Type  RTRC)  to  the side  of a  building.  [230.24(A)  Exception
               nonmetallic conduit, electrical metallic tubing or cable armor. [250.64(B)]
             e. Where not protected, 6 AWG grounding electrode conductor shall closely  No. 4]
               follow a structural surface for physical protection. The supports shall be  5. Where the voltage between conductors does not
               spaced not more than 24 inches on center and shall be within 12 inches of
               any enclosure or termination. [250.64(B)]                    exceed 300 and the roof area is guarded or iso-
             f. Where the grounding electrode conductor or bonding jumper connected to  lated, a reduction in clearance to 3 feet (914 mm)
               a  single  or  multiple  rod,  pipe,  or  plate  electrode(s) or  any  combination  shall be permitted. [230.24(A) Exception No. 5]
               thereof, as described in Section E3608.3, does not extend on to other types
               of  electrodes  that  require  a  larger  size  of  conductor,  the  grounding  E3604.2.2 Vertical clearance from grade. Overhead ser-
               electrode conductor shall not be required to be larger than 6 AWG copper  vice conductors shall have the following minimum clear-
               or  4  AWG  aluminum.  Where  the  grounding  electrode  conductor  or  ances from final grade:
               bonding  jumper  connected  to  a  single  or  multiple  concrete-encased
               electrode(s),  as  described  in  Section  E3608.1.2,  does  not  extend  on  to  1. For  conductors  supported  on  and  cabled  together
               other  types  of  electrodes  that  require  a  larger  size  of  conductor,  the  with a grounded bare messenger wire, the minimum
               grounding electrode conductor shall not be required to be larger than 4
               AWG copper conductor. [250.66(A) and (B)]                 vertical clearance shall be 10 feet (3048 mm) at the