Page 733 - 2018_IRC
P. 733

SERVICES



             Where multiple concrete-encased electrodes are present  electrode of one grounding system shall be not less than 6 feet
           at a building or structure, only one shall be required to be  (1829 mm) from any other electrode of another grounding sys-
           bonded into the grounding electrode system. [250.52(A)(3)]  tem. Two or more grounding electrodes that are effectively
           E3608.1.3  Ground  rings.  A  ground  ring  encircling  the  bonded  together  shall  be  considered  as  a  single  grounding
           building or structure, in direct contact with the earth at a  electrode system. That portion of a bonding jumper that is the
           depth below the earth’s surface of not less than 30 inches  sole connection to a rod, pipe or plate electrode shall not be
           (762 mm), consisting of at least 20 feet (6096 mm) of bare  required to be larger than 6 AWG copper or 4 AWG aluminum
           copper conductor not smaller than 2 AWG shall be consid-  wire. [250.53(A)(1), 250.53(B), 250.53(E)]
           ered as a grounding electrode. [250.52(A)(4)]      E3608.4  Supplemental  electrode  required.  A  single  rod,
           E3608.1.4 Rod and pipe electrodes. Rod and pipe elec-  pipe,  or  plate  electrode  shall  be  supplemented  by  an  addi-
           trodes not less than 8 feet (2438 mm) in length and con-  tional  electrode  of  a  type  specified  in  Sections  E3608.1.2
           sisting of the following materials shall be considered as a  through  E3608.1.6.  The  supplemental  electrode  shall  be
           grounding electrode:                               bonded to one of the following:
              1. Grounding electrodes of pipe or conduit shall not be  1. A rod, pipe, or plate electrode.
                                  3
                smaller than trade size  /  (metric designator 21) and,  2. A grounding electrode conductor.
                                    4
                where of iron or steel, shall have the outer surface  3. A grounded service-entrance conductor.
                galvanized or otherwise metal-coated for corrosion
                protection.                                      4. A nonflexible grounded service raceway.
              2. Rod-type grounding electrodes of stainless steel and  5. A grounded service enclosure.
                copper or zinc-coated steel shall be at least  / inch  Where multiple rod, pipe, or plate electrodes are installed
                                                     5
                                                      8
                (15.9 mm) in diameter unless listed. [250.52(A)(5)]  to meet the requirements of this section, they shall not be less
              E3608.1.4.1 Installation. The rod and pipe electrodes  than 6 feet (1829 mm) apart. [250.53(A)(2) and (A)(3)]
              shall be installed such that at least 8 feet (2438 mm) of  Exception: Where a single rod, pipe, or plate grounding
              length is in contact with the soil. They shall be driven  electrode has a resistance to earth of 25 ohms or less, the
              to a depth of not less than 8 feet (2438 mm) except that,  supplem   electr   sh   no      required.
              where rock bottom is encountered, electrodes shall be  [250.53(A)(2) Exception]
              driven  at  an  oblique  angle  not  to  exceed  45  degrees  E3608.5 Aluminum electrodes. Aluminum electrodes shall
              (0.79  rad)  from  the  vertical  or  shall  be  buried  in  a  not be permitted. [250.52(B)(2)]
              trench that is at least 30 inches (762 mm) deep.  The
              upper end of the electrodes shall be flush with or below  E3608.6 Metal underground  gas  piping  system. A  metal
              ground level except where the above-ground end and  underground gas piping system shall not be used as a ground-
              the grounding electrode conductor attachment are pro-  ing electrode. [250.52(B)(1)]
              tected against physical damage. (250.53(G)]     E3608.7 Pool, spa and hot tub structures and structural
           E3608.1.5  Plate  electrodes.  A  plate  electrode  that  reinforcing  steel.  The  structures  and  structural  reinforcing
           exposes not less than 2 square feet (0.186 m ) of surface to  steel described in Section E4204.2, Items 1 and 2, shall not be
                                               2
           exterior soil shall be considered as a grounding electrode.  used as a grounding electrode.
           Electrodes of bare or electrically conductive coated iron or
                                      1
           steel plates shall be not less than  /  inch (6.4 mm) in thick-
                                       4
           ness. Solid, uncoated electrodes of nonferrous metal shall          SECTION E3609
           be  not  less  than  0.06  inch  (1.5  mm)  in  thickness.  Plate      BONDING
           electrodes shall be installed not less than 30 inches (762  E3609.1 General. Bonding shall be provided where neces-
           mm) below the surface of the earth. [250.52(A)(7)]  sary to ensure electrical continuity and the capacity to con-
           E3608.1.6 Other electrodes. In addition to the grounding  duct safely any fault current likely to be imposed. (250.90)
           electrodes  specified  in  Sections  E3608.1.1  through  E3609.2 Bonding of equipment for services. The noncur-
           E3608.1.5, other listed grounding electrodes shall be per-  rent-carrying metal parts of the following equipment shall be
           mitted. [250.52(A)(6)]                             effectively bonded together:
         E3608.2  Bonding jumper. The  bonding  jumper(s)  used  to  1. Raceways or service cable armor or sheath that enclose,
         connect  the  grounding  electrodes  together  to  form  the  contain, or support service conductors.
         grounding electrode system shall be installed in accordance  2. Service  enclosures  containing  service  conductors,
         with Sections E3610.2, and E3610.3, shall be sized in accor-  including  meter  fittings,  and  boxes,  interposed  in  the
         dance with Section E3603.4, and shall be connected in the  service raceway or armor. [250.92(A)]
         manner specified in Section E3611.1. [250.53(C)]     E3609.3 Bonding for communications systems. Communi-
         E3608.3  Rod,  pipe  and  plate  electrode  requirements.  cations  system  bonding  terminations  shall  be  connected  in
         Where  practicable,  rod,  pipe  and  plate  electrodes  shall  be  accordance with Section E3609.3.1 or E3609.3.2. (250.94)
         embedded below permanent moisture level. Such electrodes
         shall be free from nonconductive coatings such as paint or  E3609.3.1 Intersystem bonding termination device. An
         enamel. Where more than one such electrode is used, each  intersystem  bonding  termination  (IBT)  for  connecting


         708                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.