Page 734 - 2018_IRC
P. 734

SERVICES



               intersystem bonding conductors shall be provided external  E3609.4.1  Grounded  service  conductor.  Equipment
               to enclosures at the service equipment or metering equip-  shall  be  bonded  to  the  grounded  service  conductor  in  a
               ment  enclosure  and  at  the  disconnecting  means  for  any  manner provided in this code.
               additional  buildings  or  structures.  An  IBT  shall  comply  E3609.4.2  Threaded  connections.  Equipment  shall  be
               with all of the following:                            bonded  by  connections  using  threaded  couplings  or
                  1. It shall be accessible for connection and inspection.  threaded  hubs  on  enclosures.  Such  connections  shall  be
                  2. It shall consist of a set of terminals with the capacity  made wrench tight.
                    for  connection  of  not  less  than  three  intersystem  E3609.4.3 Threadless couplings and connectors. Equip-
                    bonding conductors.                              ment shall be bonded by threadless couplings and connec-
                                                                     tors  for  metal  raceways  and  metal-clad  cables.  Such
                  3. It shall not interfere with opening of the enclosure
                    for  a  service,  building  or  structure  disconnecting  couplings  and  connectors  shall  be  made  wrench  tight.
                    means, or metering equipment.                    Standard  locknuts  or  bushings  shall  not  be  used  for  the
                                                                     bonding required by this section.
                  4. Where located at the service equipment, it shall be
                    securely  mounted  and  electrically  connected  to  an  E3609.4.4 Other devices. Equipment shall be bonded by
                    enclosure  for  the  service  equipment,  to  the  meter  other listed devices, such as bonding-type locknuts, bush-
                    enclosure, or to an exposed nonflexible metallic ser-  ings and bushings with bonding jumpers. [250.92(B)]
                    vice raceway, or shall be mounted at one of these  E3609.5  Sizing  supply-side  bonding  jumper  and  main
                    enclosures and connected to the enclosure or to the  bonding jumper. The bonding jumper shall not be smaller
                    grounding  electrode  conductor  with  a  6  AWG  or  than the sizes shown in Table E3603.4 for grounding elec-
                    larger copper conductor.                      trode conductors. Where the service-entrance conductors are
                  5. Where  located  at  the  disconnecting  means  for  a  paralleled in two or more raceways or cables, and an individ-
                    building  or  structure,  it  shall  be  securely  mounted  ual  supply-side  bonding  jumper  is  used  for  bonding  these
                    and electrically connected to the metallic enclosure  raceways or cables, the supply-side bonding jumper for each
                    for the building or structure disconnecting means, or  raceway or cable shall be selected from Table E3603.4 based
                    shall  be  mounted  at  the  disconnecting  means  and  on the size of the ungrounded supply conductors in each race-
                    connected to the metallic enclosure or to the ground-  way or cable. A single supply-side bonding jumper installed
                    ing  electrode  conductor  with  a  6  AWG  or  larger  for bonding two or more raceways or cables shall be sized in
                    copper conductor.                             accordance with Table E3603.4  based on the largest set of
                                                                  parallel ungrounded supply conductors. [250.102(C)]
                  6. It  shall be listed as grounding and bonding equip-
                    ment. [250.94(A)]                             E3609.6 Metal water piping bonding. The metal water pip-
                                                                  ing system shall be bonded to the service equipment enclo-
                  Exception: Means for connecting intersystem bonding  sure,  the  grounded  conductor  at  the  service,  the  grounding
                  conductors  are  not  required  where  communications  electrode conductor where of sufficient size, or to the one or
                  systems are not likely to be used.              more grounding electrodes used. The bonding jumper shall be
               E3609.3.2 An aluminum or copper busbar not less than  / 4  sized in accordance with Table E3603.4. The points of attach-
                                                            1
               inch thick by 2 inches wide (6.4 mm by 51 mm) and of  ment  of  the  bonding  jumper(s)  shall  be  accessible.
               sufficient length to accommodate not fewer than three ter-  [250.104(A) and 250.104(A)(1)]
               minations for communications systems in addition to other  E3609.7 Bonding other metal piping. Where installed in or
               connections  shall  be  provided.  The  busbar  shall  be  attached  to  a  building  or  structure,  metal  piping  systems,
               securely  fastened  and  shall  be  installed  in  an  accessible  including gas piping, capable of becoming energized shall be
               location. Connections shall be made by a listed connector.  bonded  to  the  service  equipment  enclosure,  the  grounded
               Where aluminum busbars are used, the installation shall  conductor at the service, the grounding electrode conductor
               comply with Section E3610.2.                       where of sufficient size, or to the one or more grounding elec-
                  Exception: Means for connecting intersystem bonding  trodes used. The bonding conductor(s) or jumper(s) shall be
                  conductors  are  not  required  where  communications  sized  in  accordance  with  Table  E3908.12  and  equipment
                  systems are not likely to be used.              grounding conductors shall be sized in accordance with Table
             E3609.4 Method of bonding at the service. Bonding jump-  E3908.12 using the rating of the circuit capable of energizing
             ers  meeting  the  requirements  of  this  chapter  shall  be  used  the piping. The equipment grounding conductor for the cir-
             around  impaired  connections,  such  as  reducing  washers  or  cuit that is capable of energizing the piping shall be permitted
             oversized, concentric, or eccentric knockouts. Standard lock-  to serve as the bonding means. The points of attachment of
             nuts or bushings shall not be the only means for the bonding  the bonding jumper(s) shall be accessible. [250.104(B)]
             required by this section but shall be permitted to be installed
             to make mechanical connections of raceways. Electrical con-
             tinuity  at  service  equipment,  service  raceways  and  service     SECTION E3610
             conductor enclosures shall be ensured by one or more of the  GROUNDING ELECTRODE CONDUCTORS
             methods specified in Sections E3609.4.1 through E3609.4.4.  E3610.1  Continuous.  The  grounding  electrode  conductor
                                                                  shall be installed in one continuous length without splices or
                                                                  joints  and shall  run  to  any  convenient  grounding  electrode


             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               709