SERVICES



         available in the grounding electrode system where the other  Where  a  raceway  is  used  as  protection  for  a  grounding
         electrode(s),  if  any,  are  connected  by  bonding  jumpers  in  conductor, the installation shall comply with the requirements
         accordance with Section E3608.2, or to one or more ground-  of Chapter 38. [250.64(E)(1), (2), (3), (4)]
         ing electrode(s) individually. The grounding electrode con-  E3610.4 Prohibited use. An equipment grounding conductor
         ductor  shall  be  sized  for  the  largest  grounding  electrode  shall  not  be  used  as  a  grounding  electrode  conductor.
         conductor required among all of the electrodes connected to  (250.121)
         it. [250.64(C)]
                                                                 Exception: A wire-type equipment grounding conductor
           Exception: Splicing of the grounding electrode conductor  shall be permitted to serve as both an equipment grounding
           by  irreversible  compression-type  connectors  listed  as  conductor  and  a  grounding  electrode  conductor  where
           grounding and  bonding equipment or by the  exothermic  installed  in accordance with the applicable requirements
           welding process shall not be prohibited. [250.64(C)(1)]  for  both  the  equipment  grounding  conductor  and  the
         E3610.2  Securing  and  protection  against  physical  dam-  grounding  electrode  conductor  in  Chapters  36  and  39.
         age. Where exposed, a grounding electrode conductor or its  Where used as a grounding electrode conductor, the wire-
         enclosure shall be securely fastened to the surface on which it  type equipment grounding conductor shall be installed and
         is carried. Grounding electrode conductors shall be permitted  arranged in a manner that will prevent objectionable cur-
         to be installed on or through framing members. A 6 AWG or  rent. [250.121 Exception, 250.6(A)]
         larger copper or aluminum grounding electrode conductor not
         exposed  to  physical  damage  shall  be  permitted  to  be  run
         along the surface of the building construction without metal          SECTION E3611
         covering or protection. A 6 AWG or larger copper or alumi-  GROUNDING ELECTRODE CONDUCTOR
         num grounding electrode exposed to physical damage shall  CONNECTION TO THE GROUNDING ELECTRODES
         be in rigid metal conduit, intermediate metal conduit, rigid  E3611.1 Methods  of  grounding  conductor connection  to
         polyvinyl  chloride  (PVC),  nonmetallic  conduit,  reinforced  electrodes.  The  grounding  or  bonding  conductor  shall  be
         thermosetting resin (RTRC-XW) nonmetallic conduit, elec-  connected to the grounding electrode by exothermic welding,
         trical  metallic  tubing  or  cable  armor.  Grounding  electrode  listed lugs, listed pressure connectors, listed clamps or other
         conductors smaller than 6 AWG shall be in rigid metal con-  listed means. Connections depending on solder shall not be
         duit,  intermediate  metal  conduit,  rigid  polyvinyl  chloride  used. Ground clamps shall be listed for the materials of the
         (PVC)  nonmetallic  conduit,  reinforced  thermoseting  resin  grounding electrode and the grounding  electrode conductor
         (RTRC-XW) nonmetallic conduit, electrical metallic tubing  and, where used on pipe, rod or other buried electrodes, shall
         or cable armor. Grounding electrode conductors and ground-  also be listed for direct soil burial or concrete encasement.
         ing electrode bonding jumpers in contact with the earth shall  Not  more  than  one  conductor  shall  be  connected  to  the
         not be required to comply with Section E3803, but shall be  grounding electrode by a single clamp or fitting unless the
         buried or otherwise protected if subject to physical damage.  clamp or fitting is listed for multiple conductors. One of the
         [250.64(B)]                                          methods indicated in the following items shall be used:
           Bare aluminum or copper-clad aluminum grounding elec-  1. A  pipe  fitting,  pipe  plug  or  other  approved  device
         trode  conductors  shall  not  be  used  where  in  direct  contact  screwed into a pipe or pipe fitting.
         with masonry or the earth or where subject to corrosive con-
         ditions. Where used outside, aluminum or copper-clad alumi-  2. A listed bolted clamp of cast bronze or brass, or plain
         num  grounding  electrode  conductors  shall  not  be  installed  or malleable iron.
         within 18 inches (457 mm) of the earth. [250.64(A)]     3. For  indoor  communications  purposes  only,  a  listed
         E3610.3  Raceways  and  enclosures  for  grounding  elec-  sheet  metal  strap-type  ground  clamp  having  a  rigid
         trode  conductors.  Ferrous  metal  raceways  and  enclosures  metal base that seats on the electrode and having a strap
         for grounding electrode conductors shall be electrically con-  of such material and dimensions that it is not likely to
         tinuous from the point of attachment to cabinets or equipment  stretch during or after installation.
         to the grounding electrode, and shall be securely fastened to  4. Other equally substantial approved means. (250.70)
         the  ground  clamp  or  fitting.  Ferrous  metal  raceways  and  E3611.2 Accessibility. All mechanical elements used to ter-
         enclosures  shall  be  bonded  at  each  end  of  the  raceway  or  minate a grounding electrode conductor or bonding jumper to
         enclosure to the grounding electrode or to the grounding elec-  the  grounding  electrodes  that  are  not  buried  or  concrete
         trode conductor to create an electrically parallel path. Nonfer-  encased shall be accessible. [250.68(A) and 250.68(A) Excep-
         rous metal raceways and enclosures shall not be required to  tion]
         be electrically continuous. Bonding methods in compliance
         with Section E3609.4 for installations at service equipment  E3611.3 Effective grounding path. The connection of the
         locations and with Sections E3609.4.2 through E3609.4.4 for  grounding  electrode  conductor  or  bonding  jumper  shall  be
         other than service equipment locations shall apply at each end  made in a manner that will ensure a permanent and effective
         and  to  all  intervening  ferrous  raceways,  boxes,  and  enclo-  grounding path. Where necessary to ensure effective ground-
         sures between the cabinets or equipment and the grounding  ing for a metal piping system used as a grounding electrode,
         electrode. The bonding jumper for a grounding electrode con-  effective bonding  shall  be  provided around insulated  joints
         ductor  raceway  shall  be  the  same  size  or  larger  than  the  and sections and around any equipment that is likely to be
         required enclosed grounding electrode conductor.     disconnected  for  repairs  or  replacement.  Bonding  jumpers