BRANCH CIRCUIT AND FEEDER REQUIREMENTS



                          TABLE E3702.14 (Table 210.24)           less  than  one  120-volt,  20-ampere  branch  circuit  shall  be
                   BRANCH-CIRCUIT REQUIREMENTS-SUMMARY a, b       installed to supply receptacle outlets in attached garages and
                                            CIRCUIT RATING        in detached garages with electric power. This circuit shall not

                                       15 amp    20 amp   30 amp   have other outlets.
             Conductors:                                             Exception: This circuit shall be permitted to supply read-
               Minimum size (AWG)        14       1       10         ily accessible outdoor receptacle outlets.
               circuit conductors
                                                                  E3703.6 Number of branch circuits. The minimum number
             Maximum overcurrent-
               protection device rating  15       2       30      of branch circuits shall be determined from the total calcu-
               Ampere rating                                      lated load and the size or rating of the circuits used. The num-
             Outlet devices:                                      ber of circuits shall be sufficient to supply the load served. In
               Lampholders permitted  Any type   Any type  N/A    no case  shall the  load on any  circuit  exceed the  maximum
               Receptacle rating (amperes)   15 maximum  15 or 20   30   specified by Section E3702. [210.11(A)]
             Maximum load (amperes)      15       20      30      E3703.7  Branch-circuit  load  proportioning.  Where  the
                                                                  branch-circuit  load  is  calculated  on  a  volt-amperes-per-
             a. These gages are for copper conductors.            square-foot (m ) basis, the wiring system, up to and including
                                                                              2
             b. N/A = Not Allowed.
                                                                  the  branch-circuit  panelboard(s),  shall  have  the  capacity  to
                                                                  serve  not  less  than  the  calculated  load.  This  load  shall  be
                              SECTION E3703                       evenly proportioned among multioutlet branch circuits within
                       REQUIRED BRANCH CIRCUITS                   the panelboard(s). Branch-circuit overcurrent devices and cir-
             E3703.1 Branch circuits for heating. Central heating equip-  cuits shall only be required to be installed to serve the con-
             ment other than fixed electric space heating shall be supplied  nected load. [210.11(B)]
             by an individual branch circuit. Permanently connected air-
             conditioning  equipment,  and  auxiliary  equipment  directly
             associated with the central heating equipment such as pumps,          SECTION E3704
             motorized valves, humidifiers and electrostatic air cleaners,    FEEDER REQUIREMENTS
             shall not be prohibited from connecting to the same branch  E3704.1  Conductor  size.  Feeder  conductors  that  do  not
             circuit as the central heating equipment. (422.12 and 422.12  serve 100 percent of the dwelling unit load and branch-circuit
             Exceptions No. 1 and No. 2)                          conductors shall be of a size sufficient to carry the load as
                                                                  determined  by  this chapter.  Feeder  conductors  shall  not  be
             E3703.2 Kitchen and dining area receptacles. A minimum
             of two 20-ampere-rated branch circuits shall be provided to  required to be larger than the service-entrance conductors that
             serve  all  wall  and  floor  receptacle  outlets  located  in  the  supply the dwelling unit. The load for feeder conductors that
             kitchen, pantry, breakfast area, dining area or similar area of a  serve as the main power feeder to a dwelling unit shall be
             dwelling. The kitchen countertop receptacles shall be served  determined  as  specified  in  Chapter  36  for  services.
             by a minimum of two 20-ampere-rated branch circuits, either  [310.15(B)(7)(2) and (3)]
             or  both  of  which  shall  also  be  permitted  to  supply  other  E3704.2 Feeder loads. The minimum load in volt-amperes
             receptacle outlets in the same kitchen, pantry, breakfast and  shall  be  calculated  in  accordance  with  the  load  calculation
             dining  area  including  receptacle  outlets  for  refrigeration  procedure  prescribed  in  Table  E3704.2(1).  The  associated
             appliances. [210.11(C)(1) and 210.52(B)(1) and (B)(2)]  table  demand  factors  shall  be  applied  to  the  actual  load  to
                                                                  determine the minimum load for feeders. (220.40)
               Exception: The receptacle outlet  for refrigeration appli-
               ances shall be permitted to be supplied from an individual  E3704.3 Feeder neutral load. The feeder neutral load shall
               branch circuit rated 15 amperes or greater. [210.52(B)(1)  be the maximum unbalance of the load determined in accor-
               Exception No. 2]                                   dance with this chapter. The maximum unbalanced load shall
                                                                  be the maximum net calculated load between the neutral and
             E3703.3  Laundry  circuit.  A  minimum  of  one  20-ampere-
             rated branch circuit shall be provided for receptacles located  any one ungrounded conductor. For a feeder or service sup-
             in  the  laundry  area  and  shall  serve  only  receptacle  outlets  plying electric ranges, wall-mounted ovens, counter-mounted
             located in the laundry area. [210.11(C)(2)]          cooking units and electric dryers, the maximum unbalanced
                                                                  load  shall  be  considered  as  70  percent  of  the  load  on  the
             E3703.4 Bathroom branch circuits. A minimum of one 20-  ungrounded conductors. [220.61(A) and (B)]
             ampere branch circuit shall be provided to supply bathroom
             receptacle outlet(s). Such circuits shall have no other outlets.  E3704.4 Lighting and general use receptacle load. A unit
             [210.11(C)(3)]                                       load of not less than 3 volt-amperes shall constitute the mini-
                                                                  mum lighting and general use receptacle load for each square
               Exception: Where the 20-ampere circuit supplies a single  foot of floor area (33 VA for each square meter of floor area).
               bathroom,  outlets  for  other  equipment  within  the  same  The floor area for each floor shall be calculated from the out-
               bathroom shall be permitted to be supplied in accordance  side dimensions of the building. The calculated floor area shall
               with Section E3702. [210.11(C)(3) Exception]       not include open porches, garages, or unused or unfinished
             E3703.5 Garage branch circuits. In addition to the number  spaces not adaptable for future use. [220.12, Table 220.12, and
             of branch circuits required by other parts of this section, not  220.14(J)]