Page 736 - 2018_IRC
P. 736

SERVICES



             shall be of sufficient length to permit removal of such equip-
             ment  while  retaining  the  integrity  of  the  grounding  path.
             [250.68(B)]
             E3611.4  Interior  metal  water  piping.  Where  grounding
             electrode conductors and bonding jumpers are connected to
             interior metal water piping as a means to extend the ground-
             ing electrode conductor connection to an electrode(s), such
             piping shall be located not more than 5 feet (1524 mm) from
             the point of entry into the building.
               Where interior metal water piping is used as a conductor to
             interconnect  electrodes that  are  part of the  grounding  elec-
             trode system, such piping shall be located not more than 5
             feet  (1524  mm)  from  the  point  of  entry  into  the  building.
             [250.68(C)(1)]
             E3611.5 Rebar type concrete-encased electrode. Where a
             grounding  electrode  conductor  or  bonding  jumper  is  con-
             nected to a rebar extended from the location of a rebar-type
             concrete-encased electrode installed in accordance with Sec-
             tion E3608.1.2, the point of connection to the rebar extension
             shall be in an accessible location that is not subject to corro-
             sion of the rebar. The rebar extension shall not be exposed to
             contact with the earth without corrosion protection. [250.68
             (C) (3)]
             E3611.6 Protection of ground clamps and fittings. Ground
             clamps  or  other  fittings  shall  be  approved  for  applications
             without protection or shall be protected from physical dam-
             age by installing them where they are not likely to be dam-
             aged  or  by  enclosing  them  in  metal,  wood  or  equivalent
             protective coverings. (250.10)
             E3611.7  Clean  surfaces.  Nonconductive  coatings  (such  as
             paint, enamel and lacquer) on equipment to be grounded shall
             be removed from threads and other contact surfaces to ensure
             good  electrical  continuity  or  shall  be  connected  by  fittings
             that make such removal unnecessary. (250.12)