BRANCH CIRCUIT AND FEEDER REQUIREMENTS



         used, the ampere rating or setting of the specified over-current  E3702.10  Branch  circuits  serving  heating  loads.  Electric
         device shall determine the circuit rating. (210.18)  space-heating and water-heating appliances shall be consid-
         E3702.3 Fifteen- and 20-ampere branch circuits. A 15- or  ered to be continuous loads. Branch circuits supplying two or
         20-ampere branch circuit shall be permitted to supply lighting  more outlets for fixed electric space-heating equipment shall
         units,  or  other  utilization  equipment,  or  a  combination  of  be rated not over 30 amperes. [424.3(A)]
         both. The rating of any one cord-and-plug-connected utiliza-  E3702.11  Branch  circuits  for  air-conditioning  and  heat
         tion equipment not fastened in place shall not exceed 80 per-  pump equipment. The ampacity of the conductors supplying
         cent of the branch-circuit ampere rating. The total rating of  multimotor and combination load equipment shall be not less
         utilization equipment fastened in place, other than luminaires,  than the minimum circuit ampacity marked on the equipment.
         shall not exceed 50 percent of the branch-circuit ampere rat-  The branch-circuit overcurrent device rating shall be the size
         ing where lighting units, cord-and-plug-connected utilization  and type marked on the appliance. [440.4(B), 440.35]
         equipment not fastened in place, or both, are also supplied.  E3702.12 Branch circuits serving room air conditioners.
         [210.23(A)(1) and (2)]                               A room air conditioner shall be considered as a single motor
         E3702.4  Thirty-ampere  branch  circuits.  A  30-ampere  unit in determining its branch-circuit requirements where all
         branch circuit shall be permitted to supply fixed utilization  the following conditions are met:
         equipment. A rating of any one cord-and-plug-connected uti-  1. It is cord- and attachment plug-connected.
         lization equipment shall not exceed 80 percent of the branch-
         circuit ampere rating. [210.23(B)]                      2. The rating is not more than 40 amperes and 250 volts;
                                                                   single phase.
         E3702.5 Branch circuits serving multiple loads or outlets.
         General-purpose branch circuits shall supply lighting outlets,  3. Total rated-load current is shown on the room air-condi-
         appliances,  equipment  or  receptacle  outlets,  and  combina-  tioner nameplate rather than individual motor currents.
         tions of such. Multioutlet branch circuits serving lighting or  4. The  rating  of  the  branch-circuit  short-circuit  and
         receptacles shall be limited to a maximum branch-circuit rat-  ground-fault  protective  device  does  not  exceed  the
         ing of 20 amperes. [210.23(A), (B), and (C)]              ampacity of the branch-circuit conductors, or the rating
                                                                   of  the  branch-circuit  conductors,  or  the  rating  of  the
         E3702.6 Branch circuits serving a single motor. Branch-   receptacle, whichever is less. [440.62(A)]
         circuit  conductors  supplying  a  single  motor  shall  have  an
         ampacity not less than 125 percent of the motor full-load cur-  E3702.12.1  Where  no  other  loads  are  supplied.  The
         rent rating. [430.22(A)]                                total  marked  rating of a cord- and  attachment plug-con-
                                                                 nected room air conditioner shall not exceed 80 percent of
         E3702.7  Branch  circuits  serving  motor-operated  and  the rating of a branch circuit where no other appliances are
         combination loads. For circuits supplying loads consisting  also supplied. [440.62(B)]
         of  motor-operated  utilization  equipment  that  is  fastened  in
                                         1
         place and that has a motor larger than  /  horsepower (0.093  E3702.12.2  Where  lighting  units  or  other  appliances
                                          8
         kW) in combination with other loads, the total calculated load  are also supplied. The total marked rating of a cord- and
         shall be based on 125 percent of the largest motor load plus  attachment plug-connected room air conditioner shall not
         the sum of the other loads. [220.18(A)]                 exceed 50 percent of the rating of a branch circuit where
                                                                 lighting or other appliances are also supplied. Where the
         E3702.8 Branch-circuit inductive and LED lighting loads.  circuitry is interlocked to prevent simultaneous operation
         For circuits supplying luminaires having ballasts or LED driv-  of the room air conditioner and energization of other out-
         ers, the calculated load shall be based on the total ampere rat-  lets  on  the  same  branch  circuit,  a  cord-  and  attachment
         ings  of such units  and not on  the total watts  of the  lamps.  plug-connected room air conditioner shall not exceed 80
         [220.18(B)]                                             percent of the branch-circuit rating. [440.62(C)]
         E3702.9  Branch-circuit  load  for  ranges  and  cooking  E3702.13 Electric vehicle branch circuit. Outlets installed
         appliances. It shall be permissible to calculate the branch-cir-  for the purpose of charging electric vehicles shall be supplied
         cuit load for one range in accordance with Table E3704.2(2).  by an individual branch circuit. Each circuit shall not supply
         The  branch-circuit  load  for  one  wall-mounted  oven  or  one  other outlets. (625.40)
         counter-mounted cooking unit shall be the nameplate rating
         of  the  appliance.  The  branch-circuit  load  for  a  counter-  E3702.14  Branch-circuit  requirement—summary.  The
         mounted cooking unit and not more than two wall-mounted  requirements  for  circuits  having  two  or  more  outlets,  or
         ovens all supplied from a single branch circuit and located in  receptacles,  other  than  the  receptacle  circuits  of  Sections
         the same room shall be calculated by adding the nameplate  E3703.2,  E3703.3  and  E3703.4,  are  summarized  in  Table
         ratings of the individual appliances and treating the total as  E3702.14. Branch circuits in dwelling units shall supply only
         equivalent to one range. (220.55 Note 4)             loads within that dwelling unit or loads associated only with
                                                              that dwelling unit. Branch circuits installed for the purpose of
           E3702.9.1 Minimum branch circuit for ranges. Ranges  lighting, central alarm, signal, communications or other pur-
           with a rating of 8.75 kVA or more shall be supplied by a  poses for public or common areas of a two-family dwelling
           branch  circuit  having  a  minimum  rating  of  40  amperes.  shall not be supplied from equipment that supplies an individ-
           [210.19(A)(3)]                                     ual dwelling unit. (210.24 and 210.25)