BRANCH CIRCUIT AND FEEDER REQUIREMENTS


         E3705.3  Adjustment  factor  for  conductor  proximity.  selected and coordinated to not exceed the lowest tempera-
         Where the number of current-carrying conductors in a race-  ture rating of any connected termination, conductor or device.
         way  or  cable  exceeds  three,  or  where  single  conductors  or  Conductors with temperature ratings higher than specified for
         multiconductor  cables  are  stacked  or  bundled  for  distances  terminations  shall  be  permitted  to  be  used  for  ampacity
         greater than 24 inches (610 mm) without maintaining spacing  adjustment, correction, or both. Except where the equipment
         and are not installed in raceways, the allowable ampacity of  is marked otherwise, conductor ampacities used in determin-
         each conductor shall be reduced as shown in Table E3705.3.  ing equipment termination provisions shall be based on Table
         [310.15(B)(3)]                                       E3705.1. [110.14(C)]
           Exceptions:                                           E3705.4.1  Conductors  rated  60°C.  Except  where  the
                                                                 equipment is marked otherwise, termination provisions of
              1. Adjustment factors shall not apply to conductors in
                raceways having a length not exceeding 24 inches  equipment  for  circuits  rated  100  amperes  or  less,  or
                (610 mm). [310.15(B)(3)(2)]                      marked for 14 AWG through 1 AWG conductors, shall be
                                                                 used only for one of the following:
              2. Adjustment factors shall not apply to underground
                conductors entering or leaving an outdoor trench if  1. Conductors rated 60°C (140°F);
                those  conductors  have  physical  protection  in  the  2. Conductors  with  higher  temperature  ratings,  pro-
                form of rigid metal conduit, intermediate metal con-  vided that the ampacity of such conductors is deter-
                duit, or rigid nonmetallic conduit having a length not  mined based on the 60°C (140°F) ampacity of the
                exceeding  10  feet  (3048  mm)  and  the  number  of  conductor size used;
                conductors does not exceed four.[310.15(B)(3)(3)]
                                                                   3. Conductors  with  higher  temperature  ratings  where
              3. Adjustment factors shall not apply to type AC cable  the equipment is listed  and identified for use with
                or to type MC cable without an overall outer jacket  such conductors; or
                meeting all of the following conditions:
                                                                   4. For motors marked with design letters B, C, or D con-
                   3.1. Each cable has not more than three current-  ductors having an insulation rating of 75°C (167°F)
                      carrying conductors.                           or higher shall be permitted to be used provided that
                                                                     the ampacity of such conductors does not exceed the
                   3.2. The conductors are 12 AWG copper.
                                                                     75°C (167°F) ampacity. [110.14(C)(1)(a)]
                   3.3. Not more  than  20 current-carrying conduc-
                      tors are bundled, stacked or supported on bri-  E3705.4.2  Conductors  rated  75°C.  Termination  provi-
                      dle rings. [310.15(B)(3)(4)]               sions of equipment for circuits rated over 100 amperes, or
                                                                 marked for conductors larger than 1 AWG, shall be used
              4. An adjustment factor of 60 percent shall be applied  only for:
                to Type AC cable and Type MC cable where all of
                the following conditions apply:                    1. Conductors rated 75°C (167°F).
                                                                   2. Conductors with higher temperature ratings provided
                   4.1. The  cables  do  not  have  an  overall  outer
                      jacket.                                        that the ampacity of such conductors does not exceed
                                                                     the 75°C (167°F) ampacity of the conductor size used,
                   4.2. The  number  of  current-carrying  conductors  or provided that the equipment is listed and identified
                      exceeds 20.                                    for use with such conductors. [110.14(C)(1)(b)]
                   4.3. The  cables  are  stacked  or  bundled  longer  E3705.4.3  Separately  installed  pressure  connectors.
                      than  24  inches  (607  mm)  without  spacing  Separately installed pressure connectors shall be used with
                      being  maintained.  [310.15(B)(3)(4)  Excep-  conductors at the ampacities not exceeding the ampacity at
                      tion]                                      the listed and identified temperature rating of the connec-
                                                                 tor. [110.14(C)(2)]
                   TABLE E3705.3 [Table 310.15(B)(3)(a)]
              CONDUCTOR PROXIMITY ADJUSTMENT FACTORS             E3705.4.4 Conductors of Type NM cable. Conductors in
            NUMBER OF CURRENT-CARRYING   PERCENT OF VALUES IN    NM cable assemblies shall be rated at 90°C (194°F). Types
          CONDUCTORS IN CABLE OR RACEWAY    TABLE E3705.1        NM, NMC, and NMS cable identified by the markings NM-
                       4-6                      80               B, NMC-B, and NMS-B meet this requirement. The allow-
                       7-9                      70               able ampacity of Types NM, NMC, and NMS cable shall
                                                                 not exceed that of 60°C (140°F) rated conductors and shall
                      10-20                     50
                                                                 comply with Section E3705.1 and Table E3705.5.3. The
                      21-30                     45               90°C  (194°F)  rating  shall  be  permitted  to  be  used  for
                      31-40                     40               ampacity  adjustment  and  calculations  provided  that  the
                   41 and above                 35               final corrected or adjusted ampacity does not exceed that
                                                                 for a 60°C (140°F) rated conductor. Where more than two
                                                                 NM cables containing two or more current-carrying con-
         E3705.4  Temperature  limitations.  The  temperature  rating  ductors are installed, without maintaining spacing between
         associated  with  the  ampacity  of  a  conductor  shall  be  so  the cables, through the same opening in wood framing that