Page 745 - 2018_IRC
P. 745

BRANCH CIRCUIT AND FEEDER REQUIREMENTS


                          SECTION E3706
                          PANELBOARDS
         E3706.1  Panelboard  rating.  All  panelboards  shall  have  a
         rating  not  less  than  that  of  the  minimum  service  or  feeder
         capacity required for the calculated load. (408.30)
         E3706.2 Panelboard circuit identification. All circuits and
         circuit  modifications  shall  be  legibly  identified  as  to  their
         clear, evident, and specific purpose or use. The identification
         shall include an approved degree of detail that allows each
         circuit  to  be  distinguished  from  all  others.  Spare  positions
         that contain unused overcurrent devices or switches shall be
         described accordingly. The identification shall be included in
         a  circuit  directory  located  on  the  face  of  the  panelboard
         enclosure  or  inside  the  panel  door.  Circuits  shall  not  be
         described in a manner that depends on transient conditions of
         occupancy. [408.4(A)]
         E3706.3 Panelboard overcurrent protection. In addition to
         the  requirement  of  Section  E3706.1,  a  panelboard  shall  be
         protected by an overcurrent protective device having a rating
         not greater than that of the panelboard. Such overcurrent pro-
         tective device shall be located within or at any point on the
         supply side of the panelboard. (408.36)
         E3706.4  Grounded  conductor  terminations.  Each
         grounded conductor shall terminate within the panelboard on
         an individual terminal that is not also used for another con-
         ductor, except that grounded conductors of circuits with par-
         allel conductors shall be permitted to terminate on a single
         terminal  where  the  terminal  is  identified  for  connection  of
         more than one conductor. (408.41 and 408.41 Exception)
         E3706.5 Back-fed devices. Plug-in-type overcurrent protec-
         tion  devices  or  plug-in-type  main  lug  assemblies  that  are
         back-fed  and  used  to  terminate  field-installed  ungrounded
         supply conductors shall be secured in place by an additional
         fastener that requires other than a pull to release the device
         from the mounting means on the panel. [408.36(D)]



































         720                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®