Page 738 - 2018_IRC
P. 738

CHAPTER 37

                          BRANCH CIRCUIT AND FEEDER REQUIREMENTS




             ICC user note:
                About this chapter: Chapter 37 addresses the sizing of conductors for feeders and branch circuits, specifies the required branch circuits,
                provides for overcurrent protection of such conductors, specifies limitations for branch circuit loading, and addresses panel board ratings and
                protection. Design and installation processes move directly from the service to feeders and branch circuits.




                              SECTION E3701                       overcurrent device, multiwire branch circuits shall supply only
                                 GENERAL                          line-to-neutral  loads  or  only  one  appliance.  [210.4(A)  and
             E3701.1 Scope. This chapter covers branch circuits and feed-  210.4(C)]
             ers and specifies the minimum required branch circuits, the  E3701.5.1 Disconnecting means. Each multiwire branch
             allowable  loads  and the required  overcurrent  protection for  circuit shall be provided with a means that will simultane-
             branch circuits and feeders that serve less than 100 percent of  ously disconnect  all ungrounded  conductors at the point
             the  total  dwelling  unit  load.  Feeder  circuits  that  serve  100  where the branch circuit originates. [210.4(B)]
             percent of the dwelling unit load shall be sized in accordance  E3701.5.2 Grouping. The ungrounded and grounded cir-
             with the procedures in Chapter 36. [310.15(B)(7)(2)]
                                                                     cuit conductors of each multiwire branch circuit shall be
             E3701.2 Branch-circuit and feeder ampacity. Branch-cir-  grouped by wire markers, cable ties or similar means in at
             cuit and feeder conductors shall have ampacities not less than  least one location within the panelboard or other point of
             the maximum load to be served. Where a branch circuit or a  origination. [200.4(B)]
             feeder supplies continuous loads or any combination of con-  Exception: Grouping shall not be required where the
             tinuous and noncontinuous loads,  the  minimum  branch-cir-  circuit conductors enter from a cable or raceway unique
             cuit or feeder conductor size, before the application of any  to the circuit, thereby making the grouping obvious, or
             adjustment  or  correction  factors,  shall  have  an  allowable  where  the  conductors  pass  through  a  box  or  conduit
             ampacity equal to or greater than the noncontinuous load plus  body  without  a  loop  as  described  in  Section
             125  percent  of  the  continuous  load.  [210.19(A)(1)(a)  and  E3905.12.2.1  or  without  a  splice  or  termination.
             215.2(A)(1)(a)]
                                                                       [200.4(B) Exception 1 and 2].
               Exception: The grounded conductors of feeders that are
               not connected to an overcurrent device shall be permitted
               to be sized at 100 percent of the continuous and noncon-            SECTION E3702
               tinuous load. [215.1(A)(1) Exception No. 2]                   BRANCH CIRCUIT RATINGS
             E3701.3 Selection of ampacity. Where more than one calcu-  E3702.1  Branch-circuit  voltage  limitations.  The  voltage
             lated  or  tabulated  ampacity  could  apply  for  a  given  circuit  ratings of branch circuits that supply luminaires or recepta-
             length, the lowest value shall be used. [310.15(A)(2)]  cles for cord-and-plug-connected loads of up to 1,400 volt-
                                                                                      1
                                                                  amperes or of less than  /  horsepower (0.186 kW) shall be
               Exception: Where different ampacities apply to portions                 4
               of a circuit, the higher ampacity shall be permitted to be  limited to a maximum rating of 120 volts, nominal, between
               used where the total portion(s) of the circuit with the lower  conductors.
               ampacity does not exceed the lesser of 10 feet (3048 mm)  Branch  circuits  that  supply  cord-and-plug-connected  or
               or 10 percent of the total circuit. [310.15(A)(2) Exception]  permanently connected utilization equipment and appliances
                                                                                                  1
                                                                  rated  at  over  1,440  volt-amperes  or  / horsepower  (0.186
             E3701.4 Branch circuits with more than one receptacle.                                4
             Conductors of branch circuits supplying more than one recep-  kW) and greater shall be rated at 120 volts or 240 volts, nom-
             tacle for cord-and-plug-connected portable loads shall have  inal. [210.6(A), (B), and (C)]
             ampacities of not less than the rating of the branch circuit.  E3702.2 Branch-circuit ampere rating. Branch circuits shall
             [210.19(A)(2)]                                       be rated in accordance with the maximum allowable ampere
                                                                  rating or setting of the overcurrent protection device. The rat-
             E3701.5 Multiwire branch circuits. All conductors for multi-
             wire branch circuits shall originate from the same panelboard or  ing for other than individual branch circuits shall be 15, 20, 30,
             similar distribution equipment. Except where all ungrounded  40 and 50 amperes. Where conductors of higher ampacity are
             conductors  are  opened  simultaneously  by  the  branch-circuit








             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               713
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   733   734   735   736   737   738   739   740   741   742   743