Page 731 - 2018_IRC
P. 731

SERVICES



         tion to a raceway or enclosure and at intervals not exceeding  able at its supply terminals, but not less than 10,000 amperes.
         30 inches (762 mm). [230.51(A)]                      (110.9)
         E3605.8 Raceways to drain. Where exposed to the weather,  E3606.4  Marking.  Service  equipment  shall  be  marked  to
         raceways  enclosing  service-entrance  conductors  shall  be  identify it as being suitable for use as service equipment. Ser-
         listed or approved for use in wet locations and arranged to  vice  equipment  shall  be  listed  or  field  labeled.  Individual
         drain.  Where  embedded  in  masonry,  raceways  shall  be  meter  socket  enclosures  shall  not  be  considered  as  service
         arranged to drain. (230.53)                          equipment but shall be listed and rated for the voltage and
         E3605.9 Overhead service locations. Connections at service  ampacity of the service. (230.66)
         heads shall be in accordance with Sections E3605.9.1 through  Exception:  Meter  sockets  supplied  by  and  under  the
         E3605.9.7. (230.54)                                     exclusive control of an electric utility shall not be required
           E3605.9.1  Rain-tight  service  head.  Service  raceways  to be listed. (230.66 Exception)
           shall be equipped with a service head at the point of con-
           nection to service-drop or overhead conductors. The ser-
           vice  head  shall  be  listed  for  use  in  wet  locations.        SECTION E3607
           [230.54(A)]                                                      SYSTEM GROUNDING
                                                              E3607.1 System service ground. The premises wiring sys-
           E3605.9.2  Service  cable,  service  head  or  gooseneck.  tem shall be grounded at the service with a grounding elec-
           Service-entrance  cable  shall  be  equipped  with  a  service  trode conductor connected to a grounding electrode system as
           head or shall be formed into a gooseneck in an approved  required by this code. Grounding electrode conductors shall
           manner.  The  service  head  shall  be  listed  for  use  in  wet  be  sized  in  accordance  with  Table  E3603.4.  [250.20(B)(1)
           locations. [230.54(B)]
                                                              and 250.24(A)]
           E3605.9.3 Service-head location. Service heads on race-  E3607.2 Location of grounding electrode conductor con-
           ways  or  service-entrance  cables,  and  goosenecks  in  ser-  nection.  The  grounding  electrode  conductor  shall  be  con-
           vice-entrance cables, shall be located above the point of  nected to the grounded service conductor at any accessible
           attachment  of  the  service-drop or  overhead  service  con-  point from the load end of the overhead service conductors,
           ductors to the building or other structure. [230.54(C)]
                                                              service drop, underground service conductors, or service lat-
              Exception: Where it is impracticable to locate the ser-  eral  to  and  including  the  terminal  or  bus  to  which  the
              vice head or gooseneck above the point of attachment,  grounded service conductor is connected at the service dis-
              the  service  head  or  gooseneck  location  shall  be  not  connecting means. A grounding connection shall not be made
              more than 24 inches (610 mm) from the point of attach-  to any grounded circuit conductor on the load side of the ser-
              ment. [230.54(C) Exception]                     vice  disconnecting  means,  except  as  provided  in  Section
           E3605.9.4  Separately  bushed  openings.  Service  heads  E3607.3.2. [250.24(A)(1) and (A)(5)]
           shall  have  conductors  of  different  potential  brought  out  E3607.3 Buildings or structures supplied by feeder(s) or
           through separately bushed openings. [230.54(E)]    branch  circuit(s).  Buildings  or  structures  supplied  by
           E3605.9.5 Drip loops. Drip loops shall be formed on indi-  feeder(s) or branch circuit(s) shall have a grounding electrode
           vidual  conductors.  To  prevent  the  entrance  of  moisture,  or grounding electrode  system installed in accordance with
           service-entrance conductors shall be connected to the ser-  Section  E3608.  The  grounding  electrode  conductor(s)  shall
           vice-drop or overhead conductors either below the level of  be connected in a manner specified in Section E3607.3.1 or,
           the service head or below the level of the termination of  for  existing  premises  wiring  systems  only,  Section
           the service-entrance cable sheath. [230.54(F)]     E3607.3.2. Where there is no existing grounding electrode,
                                                              the grounding electrode(s) required in Section E3608 shall be
           E3605.9.6  Conductor  arrangement.  Service-entrance  installed. [250.32(A)]
           and overhead service conductors shall be arranged so that
           water  will  not  enter  service  raceways  or  equipment.  Exception:  A  grounding  electrode  shall  not  be  required
           [230.54(G)]                                           where  only  one  branch  circuit,  including  a  multiwire
                                                                 branch circuit, supplies the building or structure and the
           E3605.9.7 Secured. Service-entrance cables shall be held  branch circuit includes an equipment grounding conductor
           securely in place. [230.54(D)]
                                                                 for grounding the noncurrent-carrying parts of all equip-
                                                                 ment. For the purposes of this section, a multiwire branch
                          SECTION E3606                          circuit  shall  be  considered  as  a  single  branch  circuit.
                 SERVICE EQUIPMENT—GENERAL                       [250.32(A) Exception]
         E3606.1 Service equipment enclosures. Energized parts of  E3607.3.1 Equipment grounding conductor. An equip-
         service equipment shall be enclosed. (230.62)           ment grounding conductor as described in Section E3908
                                                                 shall be run with the supply conductors and connected to
         E3606.2 Working space. The working space in the vicinity  the building or structure disconnecting means and to the
         of service equipment shall be not less than that specified in  grounding electrode(s). The equipment grounding conduc-
         Chapter 34. (110.26)                                    tor shall be used for grounding or bonding of equipment,
         E3606.3  Available  short-circuit  current.  Service  equip-  structures or frames required to be grounded or bonded.
         ment shall be suitable for the maximum fault current avail-  The  equipment  grounding  conductor  shall  be  sized  in


         706                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   726   727   728   729   730   731   732   733   734   735   736