Acousti-Seal  ENCORE  Automated Technical Data
                                           ®
                               ®
               10 22 26 (10650) Operable Partitions



               ACOUSTI-SEAL  ENCORE  AUTOMATED SERIES TECHNICAL DATA
                                    ®
                                                  ®
               1.6 WARRANTY                                    D. Electric motor shall be (select one):
               A.  Provide written warranty by manufacturer of      1. 115-volt, 1-phase, 1 HP, 14.0 FLA
                  operable partitions agreeing to repair or replace      2. 208/230-volt, 1-phase, 1 HP, 7.0 FLA
                  any components with manufacturing defects.      3. 208/230-volt, 3-phase, 1 HP, 4.5 FLA
               B. Warranty period: Three (3) years.               4. 460-volt, 3-phase, 1 HP, 2.0 FLA
                                                                  5. 208/230-volt, 3-phase, 1-1/2 HP, 5.2 FLA
               PART 2 – PRODUCTS
                                                               2.3 PANEL CONSTRUCTION
               2.1 MANUFACTURERS, PRODUCTS, AND OPERATION      A.  Nominal 4-1/4-inch (108 mm) thick panels in
               A.  Manufacturers: Subject to compliance with      manufacturer’s standard 51-inch (1295 mm)
                  requirements, provide product by the following:  widths. All panel horizontal and vertical framing
                  1. Modernfold, Inc.                             members fabricated from minimum 16-gage
               B.  Products: Subject to compliance with the       formed steel with overlapped and welded
                 requirements, provide the following product:     corners for rigidity. Top channel is reinforced to
                  1.  Acousti-Seal  Encore  Automated - #14       support suspension system components. Frame
                                      ®
                               ®
                    & #30 Track Systems electrically operated     is designed so that full vertical edges of panels
                    continuously hinged operable partition.       are of formed steel and provide concealed
                                                                  protection of the edges of the panel skin.
               2.2 OPERATION                                   B. Panel Skin Options:
               A.  Acousti-Seal  Encore  Automated - #14 & #30      1.  Roll-formed steel wrapping around panel
                                    ®
                            ®
                  Track Systems: Series of continuously hinged flat   edge. Panel skins shall be lock formed and
                  panels, electrically operated, top supported with   welded directly to the frame for unitized
                  operable floor seals and automatic top seals.     construction. Acoustical ratings of panels with
               B. Final Closure (select one):                       this construction:
                  1.  Electric expanding jamb sealing to panel         a. 52 STC
                    edge. Manual closures or side seal closures         b. 54 STC
                    not permitted. Floor track not required or         c. 56 STC
                    permitted.                                 C.  Hinges for Pass Doors, and Pocket Doors shall be
                  2.  Electric expanding jamb sealing to panel edge   (select one):
                    with “Presto  Automation Package”. Manual      1.  Full leaf butt hinges, attached directly to panel
                              ®
                    closures or side seal closures not permitted.   frame with welded hinge anchor plates within
                    Floor track not required or permitted.  (For    panel to further support hinge mounting to
                    complete specification see Presto Package       frame. Lifetime Warranty on hinges. Hinges
                    brochure Form #2513)                            mounted into panel edge or vertical astragal
                  3.  Hinged panel with expanding panel edge with   are not acceptable.
                                                                        ®
                    removable crank. Floor track not required or      2.  SOSS  Invisible laminated hinge with antifriction
                    permitted.                                      segments mounted between each heat
                  4.  Remote closure with expanding panel edge      treated link. Hinge to be attached directly
                    with removable crank. Floor track not required   to panel frame. Welded internal hinge
                    or permitted.                                   bracket shall support the hinge and allow for
               C.  Partition shall be operated by two push button   adjustment of hinge plates. Concealed hinges
                  control stations wired in series and located on   mounted into panel edge or vertical astragal
                  opposite sides of the partition. Control stations   are not acceptable.
                  shall be activated by key switch at stack end   D.  Panel Trim: No vertical or horizontal trim required
                  of partition. Motor unit shall be reversible,   or allowed on edges of panels; minimal groove
                  continuous duty, and class A insulated. Motor   appearance at panel joints.
                  unit shall have NEMA MG 1 service factor, high   E. Panel Weight:
                  starting torque, thermal overload protection,      1. Steel Skin
                  and open/drip proof enclosure. Motor assembly         a. 52 STC – 8.2 lbs./square foot
                  shall have wiring compliant with NFPA 70, 24 volt         b. 54 STC – 9.5 lbs./square foot
                  controls, compliant with UL 508A, and speed          c. 56 STC – 11.9 lbs./square foot
                  of 28 feet/minute. The drive unit motor shall be
                  equipped with outboard limit switches to prevent   2.4 PANEL FINISHES
                  over-extension. A positive chain drive attached   A. Panel face finish shall be (select as required):
                  to the lead panel shall pull the partition across      1.  Reinforced vinyl with woven backing weighing
                  the opening. Cable, belt, or other friction type   not less than 21 ounces per lineal yard.
                  drives will not be accepted.                    2.  Reinforced heavy duty vinyl with woven
                                                                    backing weighing not less than 30 ounces per
                                                                    lineal yard.