Page 46 - Best Practice for Construction Projects
P. 46

Arc-flash PPE



                 •    Arc Flash Boundary could be larger or smaller

                      than the other boundaries.
                 •    Cal/cm2  is used in arc flash calculation to
        4. Personal Protective Equipment
                      determine the rating of flame resistant (FR)
                      clothing.

                 •    The higher the cal/cm2 value, the heavier

                      (thicker) the FR clothing.
                 •    Non-conductive safety glasses and/or arc rated
                      face shield is required.

                 •    Store PPE safely to avoid damage. All PPE must                        Arc Flash results are posted as labels
                      be inspected prior to use.                                            on electrical panels/equipment to
                                                                                            illustrate:- ARC FLASH PPE required
                 •    If a Buddy is within the Arc Flash Boundary, they
                      must wear the appropriate PPE for that hazard                         to be worn by workers.
                      category.

                 •    Electrical work with an Arc Flash Hazard greater
                      than 40 cal/cm2 is not allowed.

                 •    ALL ARC FLASH PPE MUST BE CE MARKED &
                      COMPLY TO THE RELEVANT EN STANDARD.

                 •    No panels displaying arc flash labels are to
                      be opened unless permit is in place and
                      suitable Arc Flash PPE worn. If in doubt STOP

                      and check.