Generally, the condition of the sag mill building is very similar to the information (BV reports and photos
            from Andrew Rolfe) that has been provided to Yenem prior to and during the remediation design. Yenem
            did not identify any significant difference that would affect the assessment results. Yenem has listed all the
            locations for repair or replacement in the removing sequence and repair methodology documents
            (AMLKCa-REP-101 REV 0 [Sag Mill Building Remediation Sequences] & AMLKCa-REP-102 REV 0 [Sag Mill
            Building Remediation Methodology]). Additional recommendations are listed as follows after reviewing the
            model:


            Recommendations:

                  1.    The concrete floor at  the Knelson concentrator level requires  structural  repair works. The
                        current concrete floor has spalling concrete, and the reinforcement is exposed. This might lead
                        to further reinforcement corrosion and comprise the structural integrity. Yenem recommends
                        cleaning the  drummy concrete and  corroded  reinforcement  and repatching with  concrete
                        grout.


























                  2.    Clean and blast the stair support and apply the protective coating to project specification while
                        repairing the column D4.