Page 25 - Priesgaisrine signalizacija FX 3NET_Schneider Electric_Projktavimo instrukcija_ENG
P. 25


Planning Instruction 66571758GB0 Fire Detection 25




Sequence example 2: reset during delay
Reset
Fire Silence (short press) 10s 12s Re-sound


Input (e.g. MCP in alarm state)

Fire alarm device

Fire alarm device (10s delay)


Fire Output
Fire Output (10s delay)


Fire Output (12s delay)


Note! “Silence” affects only the fire alarm device outputs.

Note! The shortest delay is always displayed on the user interface display if more than 1 delay is activated.


6.4.3 Control group use for phased evacuation

Control groups A and B can be used to support a voice alarm fire evacuation strategy in big and/or complicated
buildings or groups of buildings.

There are numerous circumstances in which a staged fire alarm arrangement may be appropriate. One typical
application is a building with phased evacuation. In high-rise buildings, in which those closest to the fire are
evacuated in the first phase, with other areas evacuated in a series of further phases. Another application is a
progressive horizontal evacuation, e.g. in hospitals.