                              5.4.1.2.3     Halogen Backup Pump (06)
                                            At least one backup HALOGEN pump must be installed with an
                                            active, automatic switchover feature to maintain the free residual
                                            HALOGEN in the event that the primary pump fails, an increase in
                                            demand occurs, or the low chlorine alarm sounds.

                              5.4.1.2.4     Chemical Injection Dosing Point (06)
                                            A check valve or nonreturn valve must be installed between the
                                            distribution halogen and pH pumps and the injection points. In
                                            addition,
                                                •  The potable water distribution halogenation and pH
                                                   chemical injection dosing points must be located on the
                                                   delivery line downstream of the potable water pumps, OR
                                                •  If the injection dosing point is before the potable water
                                                   pumps, it must be located above the chemical dosing tanks.

                   5.5        Potable Water System Halogen Monitoring

                       5.5.1   Halogen Analyzer-Chart Recorder


                          5.5.1.1    Installation

                              5.5.1.1.1     Distant Point (06)
                                            A HALOGEN analyzer-chart recorder must be installed at a distant
                                            point in the POTABLE WATER distribution system where a
                                            significant water flow exists and represents the entire distribution
                                            system. In cases where multiple distribution loops exist and no
                                            pipes connect the loops, there must be an analyzer and chart
                                            recorder for each loop.

                              5.5.1.1.2     Data Logger
                                            Electronic data loggers with CERTIFIED DATA SECURITY
                                            FEATURES  may be used in lieu of chart recorders.


                                            If used, written documentation from the data logger manufacturer,
                                            such as a letter or instruction manual, must be provided to verify
                                            that the features are secure.


                          5.5.1.2    Operation

                              5.5.1.2.1     Maintenance (06)
                                            The HALOGEN analyzer-chart recorder must be properly
                                            maintained and must be operated in accordance with the
                                            manufacturer’s instructions.