Page 81 - Vessel Sanitation Program 2018 Operations Manual
P. 81

VSP 2018 Operations Manual



                                            WATER TANK(s) must be cleaned and disinfected.

                              5.3.4.1.2     Inspection (08)
                                            POTABLE WATER TANKS must be inspected, cleaned, and
                                            disinfected at least every 2 years.

                              5.3.4.1.3     Record Retention (08)
                                            Documentation of all inspections, maintenance, cleaning, and
                                            DISINFECTION must be maintained for 12 months and must be
                                            available for review during inspections.

                                            Records must include method of DISINFECTION, concentration
                                            and contact time of the DISINFECTANT, and a recorded
                                            HALOGEN value of less than or equal to 5 ppm before the tank is
                                            put back into service.

                              5.3.4.1.4     Disinfection Residual (07 C)
                                            DISINFECTION after potential CONTAMINATION must be
                                            accomplished by increasing the free residual HALOGEN to at least
                                            50 MG/L (ppm) throughout the affected area and maintaining this
                                            concentration for 4 hours or by way of another procedure
                                            submitted to and accepted by VSP.

                                            In an emergency, this contact time may be shortened to 1 hour
                                            by increasing free residual HALOGEN to at least 200 MG/L
                                            (ppm) throughout the affected area.


                                            Refer to Annex 13.6 for DISINFECTION method examples.

                              5.3.4.1.5     Documentation (08)
                                            The free HALOGEN residual level must be documented.

                              5.3.4.1.6     Flush (08)
                                            The disinfected parts of the system must be flushed with
                                            POTABLE WATER or otherwise dechlorinated until the free
                                            residual HALOGEN is ≤5.00 MG/L (ppm). The free HALOGEN
                                            test result must be documented.

                       5.3.5   Potable Water Tank Disinfection Methods

                          5.3.5.1    Method for Disinfecting Filled Tanks (08)
                                     DISINFECTION must be accomplished by increasing the free residual
                                     HALOGEN to at least 50 MG/L (ppm) throughout the tank and
                                     maintaining it for 4 hours. Maintain a pH value of 7.8 or less. The
                                     DISINFECTION concentration and contact time must be documented.





                                                    5.0 Potable Water; 52