Page 78 - Vessel Sanitation Program 2018 Operations Manual
P. 78

VSP 2018 Operations Manual



                                            All refrigerant brine lines and nonpotable chilled water lines in all
                                            FOOD AREAS, such as on ice machines, ice cream machines, etc.,
                                            must be identified with either ISO 14726 (blue/white/blue) or by
                                            another uniquely identifiable method to prevent CROSS-
                                            CONNECTIONS.

                              5.3.2.1.2     Protection (07 C)
                                            POTABLE WATER piping must not pass under or through tanks
                                            holding nonpotable liquids.

                              5.3.2.1.3     Bunker Connection (08)
                                            The POTABLE WATER bunker filling line must begin either
                                            horizontally or pointing downward and at a point at least
                                              millimeters (18 inches) above the bunker station deck.

                              5.3.2.1.4     Cap/Keeper Chain (08)
                                            The POTABLE WATER filling line must have a screw cap
                                            fastened by a NONCORRODING cable or chain to an adjacent
                                            BULKHEAD or surface in such a manner that the cap cannot
                                            touch the deck when hanging free.


                                            The hose connections must be unique and fit only the POTABLE
                                            WATER hoses.

                              5.3.2.1.5     Identification (08)
                                            Each bunker station POTABLE WATER filling line must be
                                            striped or painted blue or in accordance with the color designation
                                            in ISO 14726 (blue/green/blue) and clearly labeled “POTABLE
                                            WATER FILLING” in letters at least 13 millimeters (0.5 inch)
                                            high, stamped on a noncorrosive label plate or the equivalent, and
                                            located at or near the point of the hose connection.

                              5.3.2.1.6     Technical Water (08)
                                            If used on the vessel, TECHNICAL WATER must be bunkered
                                            throug  separate piping using fittings incompatible for POTABLE
                                            WATER bunkering.

                                            This does not apply to water bunkered from shore-side municipal
                                            water supply.

                              5.3.2.1.7     Different Piping (08)
                                            TECHNICAL WATER must flow through a completely different
                                            piping system.