VSP 2018 Construction Guidelines



                       7.2.2    Mixing Valve
                                Supply hot and cold POTABLE WATER through a mixing valve to a faucet
                                with the appropriate BACKFLOW protection at each bucket-filling station.


                       7.2.3    Deck Drainage
                                Provide appropriate deck drainage (e.g., SCUPPER or sloping deck to DECK
                                DRAIN) under all bucket-filling stations to eliminate any pooling of water on
                                the decks below the bucket-filling station.

                   7.3    Crew Public Toilet Rooms for Food Service Employees


                       7.3.1    Location and Number
                                Install at least one employee toilet room in close proximity to the work area of
                                all FOOD PREPARATION AREAS. [Beverage-only service bars are excluded.]

                                Provide one toilet per 25 employees and provide separate facilities for males
                                and females if more than 25 employees are assigned to a FOOD
                                PREPARATION AREA (excluding wait staff). This refers to the shift with the
                                maximum number of FOOD employees excluding wait staff. Urinals may be
                                installed but do not count toward the toilet/employee ratio.

                          7.3.1.1       Main Galleys and Crew Galleys
                                        For main galleys and crew galleys, locate toilet rooms inside the FOOD
                                        PREPARATION AREA or in a passageway immediately outside the
                                        area.  If a main galley has multiple levels and there is stairwell access
                                        between the galleys, toilet rooms may be located near the stairwell
                                        within one deck above or below.

                          7.3.1.2       Other Food Service Outlets
                                        For other FOOD SERVICE outlets (lido galley, specialty galley, etc.),
                                        do not locate toilet rooms more than two decks above or below and
                                        within the distance of a fire zone. Do not locate toilet rooms more than
                                        one fire zone away if on the same deck (they should be within the same
                                        fire zone or an adjacent fire zone). If  more than one FOOD SERVICE
                                        outlet is located on the same deck, the  toilet room may be located on
                                        the same deck between the outlets and  within two fire zones of each
                                        outlet.

                          7.3.1.3       Provision Areas
                                        For preparation rooms in provision areas, use the distance requirement
                                        described in 7.3.1.2 to locate toilet rooms.

                       7.3.2    Ventilation and Handwashing
                                Install exhaust ventilation and handwashing facilities in each toilet room. Air
                                hand dryers are not permitted in these toilet rooms. Install a permanent sign in
                                English, and other languages where appropriate, stating the exact wording: