Page 47 - Vessel Sanitation Program 2018 Construction Guidelines
P. 47

VSP 2018 Construction Guidelines



                                “WASH HANDS AFTER USING THE TOILET.” Locate this sign on the
                                BULKHEAD adjacent to the main toilet room door or on the main door inside
                                the  toilet room.


                       7.3.3    Hands-Free Exit
                                Ensure hands-free exit for toilet rooms, as described in section 36.2. Ensure
                                handwashing facilities have sanitary faucet handles as in section 7.1.8.

                       7.3.4    Doors
                                Install tight-fitting, self-closing doors.


                       7.3.5    Decks
                                Construct decks of hard, durable materials and provide COVING at the
                                BULKHEAD-deck juncture.

                       7.3.6    Deckheads and Bulkheads
                                Install EASILY CLEANABLE DECKHEADS and BULKHEADS.


               8.0  Equipment Placement and Mounting

                   8.1    Seal
                          Seal counter-mounted equipment that is not PORTABLE to the BULKHEAD,
                          tabletop, countertop, or adjacent equipment.

                          If the equipment is not sealed, provide sufficient, unobstructed space for cleaning
                          around, behind, and between fixed equipment. The space provided is dependent on
                          the distance from either a position directly in front or from either side of the
                          equipment to the farthest point requiring cleaning as described in sections 8.1.1
                          through 8.1.4. These requirements do not apply to open racks, other equipment of
                          open design, or PORTABLE equipment. See also Figures 8a through 8d.

                       8.1.1    Cleaning Distance Less Than 600 Millimeters (24 Inches)
                                A cleaning distance of less than 600 millimeters (24 inches) requires an
                                unobstructed space of 150 millimeters (6 inches).

                       8.1.2    Cleaning Distance Between 600 Millimeters (24 Inches) and
                       1,200 Millimeters (48 Inches)
                                A cleaning distance between 600 millimeters (24 inches) and 1,200 millimeters
                                (48 inches) requires an unobstructed space of 200 millimeters (8 inches).


                       8.1.3    Cleaning Distance Between 1,200 Millimeters (48 Inches) and
                       1,800 Millimeters (72 Inches)
                                A cleaning distance between 1,200 millimeters (48 inches) and
                                1,800 millimeters (72 inches) requires an unobstructed space of 300 millimeters
                                (12 inches).