Page 50 - Vessel Sanitation Program 2018 Construction Guidelines
P. 50

VSP 2018 Construction Guidelines



                                has to be minimum of 300 millimeters (12 inches). For cleaning distance greater
                                than 1,800 millimeters (72 inches), the closer space has to be treated according
                                to section 8.1.4. See Figure 8d.


                   8.2    Seal or Elevate
                          Seal equipment that is not PORTABLE to the deck or elevate it on legs that provide
                          at least a 150-millimeter (6-inch) clearance between the deck and the equipment. If no
                          part of the equipment is more than 150 millimeters (6 inches) from the point of
                          cleaning access, the clearance space may be only 100 millimeters (4 inches). This
                          includes vending and dispensing machines in FOOD AREAS, including mess rooms.

                          Exceptions to the equipment requirements may be granted if there are no barriers to
                          cleaning (e.g., equipment such as waste handling systems and warewashing machines
                          with pipelines, motors, and cables) and a 150-millimeter (6-inch) clearance from the
                          deck may not be practical.

                       8.2.1    Deck Mounting
                                Continuous weld all equipment that is not PORTABLE to stainless steel pads or
                                plates on the deck. Ensure the welds have SMOOTH edges, rounded corners,
                                and no GAPS.

                       8.2.2    Adhesives
                                Attach deck-mounted equipment as an integral part of the deck surface with
                                glue, epoxy, or other durable, APPROVED adhesive product. Ensure that the
                                attached surfaces are SMOOTH and EASILY CLEANABLE.


                   8.3    Deckhead Clearance
                          Provide a minimum of at least 150 millimeters (6 inches) between equipment and
                          DECKHEADS. If this clearance cannot be achieved, extend the equipment to the
                          DECKHEAD panels and seal appropriately.

                   8.4    Foundation or Coaming
                          Provide a sealed-type foundation or coaming for equipment not mounted on legs. Do
                          not allow equipment to overhang the foundation or coaming by more than
                          100 millimeters (4 inches). Completely seal any overhanging equipment along the
                          bottom (Figure 9).

                          Mount equipment on a foundation or coaming at least 100 millimeters (4 inches)
                          above the finished deck. Use cement, hard SEALANT, or continuous weld to seal
                          equipment to the foundation or coaming.