Page 190 - FanPedia - By Twin City Fan and Blower
P. 190

FAN-PEDIA                                                                                                                                                                                                SPECIAL CONSTRUCTION

                     Published by
            Twin City Fan & Blower                                                                                                                                                                                  REGENERATIVE THERMAL OXIDIZER  (RTO)
                         ©2017                                                                 TCF.COM
                                                                                                                                                                                                GENERAL INFORMATION
                                                                                                                Continuous Weld
                                                                                                                > Weld locations vary                                                           A regenerative thermal oxidizer (RTO) is an industrial process that
                                                                                                                > See engineering standard E1-14                                                destroys  air  pollutants  emitted  from  process  exhaust.  These  gas
                                                                                                                                                                                                streams are usually produced by industrial process ventilation, i.e.
                                                                                                                Seal Weld                                                                       paint booths, printing, and paper mills. Fans are tested at the shop
                                                                                                                > Weld locations vary                                                           with a Soap Bubble Test to check for leaks.
                                                                                                                > See engineering standard E1-14
                                                                                                                                                                                                - Fan Construction
                                                                                                                Gasketing                                                                              > Solid drive side on housing (no drive plates)
                                                                                                                > Double gaskets required                                                              > Bolted connections must have close centered hole patterns
                                                                                                                                                                                                          (3” to 4” centers) Includes:  inlet and outlet flanges, access
                                                                                                                                                                                                          doors, cover plates, inlet funnels, split housings, etc.
                                                                                                                Shaft Seal                                                                             > Not recommended for applications over 600 F
                                                                                                                                                                                                                                                                                         o
                                                                                                                                                                                                       > Dampers (if required) must have stuffing boxes
                                                                                                                Pedestal Foot Gussets
                                                                                                                                                                                                - Gasketing
                                                                                                                                                                                                       > Use silicone sponge & silicone caulk
                                                                                                                Centering Plates                                                                       > Use on all connections: inlet/outlet flanges, funnel, inlet
                                                                                                                                                                                                       plate, access doors, split housing, etc.
                                                                                                                                                                                                       > If constructed with a split housing, centering plates are
                                                                                                                                                                                                       required to seal open areas by shaft seals and inlet funnel or
                                                                                                                                                                                                       inlet plate

                                                                                                                                                                                                - Shaft Seals
                                                                                                                                                                                                       > Friction type
                                                                                                                                                                                                       > Single Carbon Ring type
                                                                                                                                                                                                       > Commercially available carbon ring or others seal

                                                                                                                                                                                                - Special Requirements (sales to specify)
                                                                                                                                                                                                       > Pedestal – Concrete requirements
                                                                                                                                                                                                       > Fan Base – Construction based on how fan will be mounted
                                                                                                                                                                                                       in field
                                                                                                                                                                                                       > Fan Operation (VFD, Cycling, Bake Out conditions)






                                                                                                                                                                                                                                                                                                                  96