Page 64 - 14th @ Irving Basis of Design (internal)
P. 64

Security Equipment Room (SER)

                         Floor Finishes             Slab sealed with static dissipative coating/sealant.

                                                    Double doors with an opening 36” W X 7’ H for
                         Doors                      personnel and equipment access.  With card reader
                                                    access control.

                         Temperature Range          18º – 24 º C on a 24hr/7-day basis.

                         Humidity Range             20-55% RH on a 24/7-day basis.

                                                    Average 200 Watts/square foot depending on
                         Electrical Design Load     equipment layouts, with provisions for up to 6 KW
                                                    point loads at selected racks.

                         Convenience Power          110VAC quad outlets at 8 feet intervals along walls
                                                    and cabinet mounted

                         Equipment Power            Dedicated power panel or distribution units within
                                                    room.  Emergency power and UPS to be provided.

                         Fire Suppression           Dry pipe pre-action sprinkler system with flush
                                                    mounted heads or approved suppression agents for
                                                    occupied spaces.


                         SEC Cable Supports         Depends on layout, cabling to console is required
                                                    which may be in ladder runway suspended from
                                                    ceiling slab at 7.5 feet AFF as required over cabinet
                                                    and wall mounted equipment.
                                                    Open, basket type cable tray below access floor when
                                                    installed.

                         Grounding                  Telecom and electrical grounding requirements
                                                    apply.  Mounted in room as part of the J-TIA-607A
                                                    grounding system.  Signal reference grounding grid
                                                    in raised floor.