Page 284 - E:\CloudStation\Project\1 DONE\Ranhill CIMAH\Flip Book\
P. 284

Figure D1.2 Potential Sources of Major Accidents



 Hazardous
 No  Location  Hazard Event (Conditions leading to major accident)  Potential Major Event
 Substance

 Dropped or damaged  causing rupture of
 1  Chlorine Room  Chlorine  Toxic Gas Release / Dispersion
 weakened cylinder joint weldment / shelf


 Dropped or damaged chlorine valve, causing
 2  Chlorine Room  Chlorine  Toxic Gas Release / Dispersion
 failure of valve


 3  Chlorine Room  Chlorine  Corrosion and pitting of drum shelf or valve   Toxic Gas Release / Dispersion



 Chlorine Room
 4  Chlorine  Leak between tubing connector and header valve  Toxic Gas Release / Dispersion
 Chlorination Area


 Chlorine Room
 5  Chlorine  Leak at the tubing connector  Toxic Gas Release / Dispersion
 Chlorination Area