Page 30 - B8773-AEW-XX-XX-PP-A-0001_[P1]_Contractors Manual
P. 30

Detail 2                                          Detail 3

Upgrade of sound insulation to existing concrete  Upgrade of acoustic insulation and fire
floor slab at first floor.                        protection to existing timber floor between
                                                  existing A5 use at ground floor and existing
Unless the Developer can prove that the shell     residential use at first floor:
unit floor construction has been designed and     N.B. If existing ceiling is lath and plaster, this
constructed as a separating floor in accordance   should be supported by chicken wire securely
with the current edition of Approved Document     fixed to underside of joists.
E, then the sound insulation is to be upgraded
by Client’s contractor by the provision of:       •	 50 x 38 timber battens @ 600 centres fixed to
                                                      existing soffit
•	 50x38mm deep timber cross battens fixed to
    u/s. concrete floor @ 600 centres.            •	 16mm deep British Gypsum RB1 resilient bars
                                                      @ 400 centres
•	 16mm deep British Gypsum RB1 resilient bars
    @ 400 centres                                 •	 25mm thick absorbent layer of British
                                                      Gypsum Isover Sound Deadening Floor Roll
•	 25mm thick absorbent layer of British              within the void.
    Gypsum Isover Sound Deadening Floor Roll
    within the void.                              •	 2 layers of 12.5mm Gypsum Fireline board.

•	 One layer of 12.5mm Gyproc Wallboard TEN
    (10kg/m²)

2.5.1  Acoustic Ceilings                          3 February 2016